Ei Electronics Model Ei151TLR Ionisation, Technical Specification, Installation & Placement

Page 2

Model Ei151TLR Ionisation

Technical Specification

Sensor

Ionisation

Sensitivity:

Complies with BS 5446 Part 1:

 

2000

Source:

Americium 241

Button Test:

Simulates the effect of smoke and

 

checks electronics and horn.

Supply Voltage:

230V AC

Battery back-up:

Rechargeable lithium cells

Power-On Indicator:

Continuous green LED

Alarm:

Electronic Piezoelectric horn

 

in unit

Alarm Sound Output: 85dB (minimum) at 3m

Alarm Status:

Red LED flashes every second on

 

unit sensing fire

Temperature Range:

0° to 40°C

Humidity Range:

15% to 95% Relative Humidity

Remote control:

Ei152, Ei159 or MCP400

Interconnect:

Up to 12 interconnected

 

Ei150/151TL/151TLR/154TL/155/1

 

56TLH/156TLR smoke or heat

 

alarms, along with an EI158 relay

 

base

Fixing:

Screw fixings supplied

Plastic material:

UL94VO flame retardant

Dimensions:

140mm x 120mm x 46mm

Weight:

227g

Warranty:

5 year (limited) warranty

Approvals:

Kitemarked to BS EN 14604:2005,

 

CE Approved

Specifications are subject to change

Installation & Placement

Wiring for Interconnected Alarms

Be very careful about correctly wiring the alarms as mixing Live and Neutral will blow/damage interconnected alarms.

Alarms should be placed in accordance with the general guidelines shown in the diagram above. These recommendations are based on the problem of areas of “dead air” close to corners of rooms and apexes of ceilings, which could result in the prevention of smoke reaching the smoke detector

Please consult instruction booklet for specific installation details

Important Precaution:

Do not install the actual smoke/heat alarm itself in new or renovated buildings until all work is completed (including floor coverings) and the building has been fully cleaned. The wiring can be installed when appropriate. (Excessive dust and debris from building work can contaminate the smoke chamber and cause problems, and it will also invalidate the guarantee). If it must be installed, cover it completely, particularly around the edges, with a dust cover (eg. a plastic bag), until all cleaning is finished.. Connect wires to the unit as in wiring diagram. All wiring must comply with local codes.

Shannon Free Zone, Shannon, Co. Clare, Ireland.

Ph.+353 61 471277 Fx.+353 61 471053

Email. eielectronics@eiltd.ie

Web: www.eielectronics.com

E & OE As our policy is one of continuous product development, we reserve the right to alter product details without prior not ice.

Ei151TLR DataSht RevB

Image 2
Contents Operation Model Ei 151TLR IonisationProduct Description Model Ei151TLR Ionisation Technical SpecificationInstallation & Placement