Model Ei164R Heat
Technical Specification
Sensor | Thermistor |
|
|
Sensitivity: | Complies with BS 5446 Part 2: | Temperature Range: | 0 to 40°C |
| 2003 | Humidity Range: | 0% to 90% Relative Humidity |
Source: | Contains no radioactive material | Remote Control: | Ei152 or MCP400 |
Airspeed: | Essentially immune to the effect | Interconnect: | Up to 12 interconnected |
Button Test: | of airspeed. |
| Ei140/141/143/144/145/146/161/16 |
Simulates the effect of heat and |
| 4/166 smoke or heat alarms, along | |
Supply Voltage: | checks electronics and horn. | Fixing: | with an Ei128 relay base |
240V AC | |||
Battery back up: | Rechargeable lithium cells | Plastic material: | UL94VO flame retardant |
Continuous green LED | Dimensions: | 145mm x52mm | |
Alarm: | Electronic Piezoelectric horn | Weight: | 291g |
| in unit | Warranty: | 5 year (limited) warranty |
Alarm Sound Output: 85dB (minimum) at 3m | Approvals: | Kitemarked to | |
Alarm Status: | Red LED flashes every second on |
| Approved |
| unit sensing heat |
|
|
|
| Specifications are subject to change |
Installation & Placement
Wiring for Interconnected Alarms
Be very careful about correctly wiring the alarms as mixing Live and Neutral will blow/damage interconnected alarms.
Alarms should be placed in accordance with the general guidelines shown in the diagram above. These recommendations are based on the problem of areas of “dead air” close to corners of rooms and apexes of ceilings, which could result in the prevention of smoke reaching the smoke detector
Important Precaution:
Do not install the actual smoke/heat alarm itself in new or renovated buildings until all work is completed (including floor coverings) and the building has been fully cleaned. The wiring can be installed when appropriate. (Excessive dust and debris from building work can contaminate the smoke chamber and cause problems, and it will also invalidate the guarantee). If it must be installed, cover it completely, particularly around the edges, with a dust cover (eg. a plastic bag), until all cleaning is finished.. Connect wires to the unit as in wiring diagram. All wiring must comply with local codes.