2 Bosch Voice Evacuation Systems

Use the EVAX25EM, EVAX50EM, or EVAX100EM expander panel when a 25 W, 50 W, or 100 W audio expander is needed with its own enclosure. Use the EVAX150EM and EVAX200EM for expansion when greater power is required in the larger enclosure configuration. The EM models have all the features of the E models except they are without a paging microphone.

Optional Expander Modules

The expander modules (EVX- models) can increase the capacity of any Bosch voice evacuation system or expander panel. They do not have paging microphones and are intended for installation in UL Listed enclosures (not supplied). Features of these modules:

Audio amplifier

Power regulator and battery charger

Tone generator

Optional Zone Splitters

The EVX4Z and EVX2ZA zone splitters allow the supervised output of any Bosch audio amplifier to supervise multiple zones. Features of these zone splitters:

Manual selection of any or all voice evacuation zones for emergency paging

Automatic selection of voice evacuation zones by connecting normallyopen contacts from the FACP or other auxiliary control system

Annunciation of either active or faulted zone status by individual LEDs

Compatibility with jumperselectable 25 V and 70 V amplifier outputs

The EVX4Z has four Class B zones. The EVX2ZA has two Class A zones.

Functions

Digital Message Repeater

Each of the Bosch voice evacuation systems (EVAX25, EVAX50, EVAX100, EVAX150, and EVAX200) includes a digital message repeater (DMR). The systems come with the following standard 15second message programmed:

"Attention, please. There has been a report of an emergency. Proceed calmly to the nearest exit and leave the building immediately. Do not use the elevators; use stairwells where necessary. All handicapped occupants shall use the building evacuation plan."

The voice evacuation message is broadcast until the FACP resets or until emergency personnel interrupt the broadcast with a manual page. When the FACP resets, the voice evacuation system automatically returns to normal operating condition.

The closure of a contact from either the FACP or from any normallyopen contact device can cause the broadcast of a chime tone followed by the message "All clear."

Optional primary and secondary messages are available. For further information, refer to the Bosch Voice Evacuation

System's Optional Messages Technical Service Note (P/

N: F01U500869).

Remote Paging Microphones

Remote paging microphones (up to five per EVXSC supervisory card) are supported through a supervised circuit. Remote microphones may be mounted up to 5000 ft (1.5 km) away from the EVAX voice evacuation panel. An ideal use for a remote microphone is when the FACP and voice evacuation system panels are in an electrical room and you need a microphone in the lobby.

System Settings

Control system operation by DIP switch settings:

Configure three DIP switches to determine alert tones of Temporal Slow Whoop (default), Hi Lo, Horn, Bell, or 1 kHz.

Turn the Diagnostic Mode on or off (default).

Set the AC Power Failure Report for no delay (default) or for a sixhour delay.

Indicate if batteries are connected to the system. The default setting is batteries are connected.

Indicate if a microphone is connected to the system. The default setting is a microphone is connected.

Set the initial delay before a message starts for no delay, 4second delay, 8second delay (default),

12second delay, 16second delay, 20second delay,

24second delay, or 28second delay. The chosen tone sounds during the delay.

Set the delay between repeats of the message for a 4second delay, 8-second delay, 12second delay (default), or 16second delay.

Indicate if the message plays or not. Message on is the default.

Set the number of times the message plays to one play, two plays, three plays (default), or continuous play.

Certifications and Approvals

Region

Certification

 

USA

UL

UOXX: Control Unit Accessories, System

 

 

(UL864), UOXX2: Control Unit

 

 

Accessories, System - Component

 

 

(UL864)

 

CSFM

6911-1615: 101, 6911-1615: 102,

 

 

6911-1615: 103, and 6911-1615: 104

Installation/Configuration Notes

Compatible Products

The following products are compatible with the Bosch Voice Evacuation Systems:

Image 2
Contents Optional Expander Panels System OverviewBosch Voice Evacuation Systems Certifications and Approvals Installation/Configuration NotesFunctions Technical Specifications Mechanical Properties Power Requirements BatteryPower Requirements Primary OutputsModel Consists Model Ordering Information EVX-CAB-1R EVX-BB-2REVX-CAB-1 EVX-CAB-2