•TS: Tank Sensor (QAZ36)*
•B3: Room Control Module (QAA73)*
•B1: Room Thermostat
•B9: Outdoor Temperature Sensor (QAC34)*
•P1: Heating Pump
•PDHW: Hot Water pump
•PLP: Primary Pump (only for figure 9b)
(*) Available Optional Extra
•Pumps (Not Supplied)
•Isolating Valve (Not Supplied)
•Installer Wiring
•Hot Water Cylinder (Not Supplied)
•Low Loss Header (Not Supplied)
•Non return valve (Not supplied)
Applications (pumps, sensor, remote control ...) have to be connected to terminal as follows (see also section 14):
| WITH QAA73 | WITH | |
| REMOTE CONTROL | ROOM THERMOSTAT | |
|
|
| |
APPLICATION | TERMINAL BOARD | TERMINAL BOARD | |
|
|
| |
PRIMARY PUMP PLP (only for figure 9b) | M1: A – B | M1: A – B | |
|
|
| |
DHW PUMP PDHW | M3: 13 – 14 | M3: 13 – 14 | |
|
|
| |
HEATING PUMP P1 | M3: 11 – 12 | M3: 11 – 12 | |
|
|
|
|
DHW SENSOR TS | M2: 7 | – 8 | M2: 7 – 8 |
|
|
|
|
REMOTE CONTROL QAA73 | M2: 1 | – 2 | NO |
|
|
|
|
ROOM THERMOSTAT | M2: 3 | – 4 OPEN | M2: 3 – 4 |
|
|
|
|
Parameter changes requires (see also section 16):
PCB | Description | Setting Parameter | ||
PARAMETER | ||||
|
|
| ||
H552 | Hydraulic system | H552 | = 2 | |
|
|
|
| |
H553 | KonfigHKS | H553 | = 21 | |
|
|
|
| |
H615 | KonfigAusgang | H615 | = 9 | |
|
|
|
| |
H632 | Wanfo Q8 | H632 | = 00001100 | |
|
|
|
|
INSTRUCTIONS PERTAINING TO THE INSTALLER | 17 | 926.772.1 - GB/IE |
|
|