Table 4. Main Installer Setup Menu. (Continued)

 

 

 

 

 

 

 

 

 

Factory Setting

 

Other Choices

 

 

Installer

 

 

 

 

 

Select

Setup

Option

Description

Options

Description

Comments

Number

Cycles per

0220

3

Compressor Stage

1-6

1-6 available;

hour (cph) for

 

 

1 cycles per hour

 

3 is recommended.

 

1st Stage

 

 

(cph)

 

 

 

Compressor

 

 

 

 

 

 

Cycles per

0240

5

Conventional Heat

1-12

1-12 available; typical

Not shown if

hour (cph) for

 

 

Stage 1 cycles per

 

settings:

system selection

1st Stage

 

 

hour (cph)

 

1—1 cph used for steam or

is heat pump.

Conventional

 

 

 

 

gravity system.

Selection in this

Heat

 

 

 

 

3—3 cph used for hot water

stage changes

 

 

 

 

 

systems or high efficiency

default cph for

 

 

 

 

 

(90% or better) fossil fuel

2nd stage heat.

 

 

 

 

 

forcedairsystems.

 

 

 

 

 

 

5—5 cph used for standard

 

 

 

 

 

 

fossil fuel forced air

 

 

 

 

 

 

systems.

 

 

 

 

 

 

9—9 cph used for electric

 

 

 

 

 

 

forced air heat systems.

 

Continuous

0280

0

Backlight not on

1

Backlight is on continuously

Option is always

Backlight

 

 

continuously.

 

(thermostat must have a

shown; however,

 

 

 

Thermostat

 

common wire attached for

continuously on

 

 

 

backlight comes on

 

this function).

backlight works

 

 

 

with each key

 

 

only if thermostat

 

 

 

press.

 

 

is wired with 24

 

 

 

 

 

 

vac Common.

Additional

0290

0

Only main menu

1,2

1—Main Menu and Regional

The majority of

Menu Choices

 

 

options are shown.

 

Settings are shown plus

application

 

 

 

Installer Test

 

Installer Test (Tables 5 and 7

require only the

 

 

 

Options shown next

 

only).

Main Menu

 

 

 

(Table 7).

 

2—All remaining Menu/

Options.

 

 

 

 

 

 

 

 

 

 

 

Options shown plus Installer

 

 

 

 

 

 

Test (Tables 5, 6 and 7).

 

 

 

 

 

 

 

 

69-1700

8

Image 8
Contents Selecting Location When Installing this ProductApplication Installing Wallplate IdentificationsTypical hookup of heat-only system 1H conventional Inserting Batteries Optional Powering the ThermostatWiring 24 Vac Common Adjusting Real-Time Clock Using the Thermostat Setting Calendar and Time Mounting the ThermostatInstaller Setup OperationExiting Installer Setup Option Description Options CommentsOption is always Select Option Description Options Comments Regional Settings MenuFactory Setting Other Choices Advanced Settings Menu Factory Setting Other Choices SelectAdvanced Features Installer System TestOutdoor or Indoor Temperature Sensor System CheckoutTroubleshooting see Table Troubleshooting Symptom Possible Cause Action