The "Autospeed 24V™ | " |
Control Package: |
|
24V Digital |
|
and Fan Coil Control Board |
|
For 2 pipe and 4 pipe fan coils |
|
FAN | AUTOMATIC | |
SPEED | ||
| ® | CONTROL |
|
|
Accurate, Efficient, and Quiet Fan Coil Operation
The new Autospeed 24V™ thermostat (part #'s T200 and T201) provides 24V AC single stage tem- perature control of 2 pipe and 4 pipe fan coil applica- tions. The T200/T201 thermostat offers maximum comfort and efficiency by automatically selecting the appropriate High, Medium, or Low fan speed, de- pending on room temperature and thermostat tem- perature setting. This automatic fan speed control not only brings the room temperature to the desired set point quickly, it maintains the room temperature with the most efficient fan speed selection. Once the desired room temperature is achieved the fan coil operates on low speed for extremely quiet operation.
The fan coil control board is a circuit board that pro- vides control of a
For ceiling fan coils and vertical console units, op- tional controls are factory installed, which include the control board, transformer, and disconnect switch. For
(Shown with wall plate)
T200/T201 Thermostat Features
•Compatible with 2 pipe and 4 pipe fan coils Series HBC/PHBC/RHBC/CHBC,
HW/CWE
•Cycle fan or continuous fan operation
•
•
•Large LED digital display
•Allows less expensive 24V control wiring from the fan coil to the thermostat, rather than larger, more expensive line voltage wiring.
•
•Fan speed determination:
•If room temperature is 4 degrees (F.) off thermostat set point, fan will operate on High speed.
•If 3 degrees off set point, fan will operate on Medium speed.
•If within 2 degrees of set point, fan will operate on Low speed.
•One or 3 hour Auto override - Fan speed defaults to "Auto" mode after 1 hour if the user manually changes it to a particular fan speed.
•Temperature set range:
•Adjustable high and low temperature set points
•Selectable Fahrenheit / Centigrade display
•Power switch turns system off/on
•Requires
•No batteries required
•Set points are permanently retained in memory in case of power interruption
•Simple operation
•Mercury Free
•Wall plate included
|
| DISPLAY CODES |
|
|
|
|
| |||
DISPLAY |
| STEADY | FLASHING |
|
|
| ||||
P1 | Auto fan timer - 1 hour (default) | Auto fan timer - 3 hour | ||||||||
P2 | Continuous fan (default) | Cycled fan |
|
|
| |||||
P3 | o | F (default) | o | C |
|
|
| |||
|
|
|
|
| ||||||
P4 | Cycled fan standard | Cycled fan overdrive | ||||||||
|
|
|
|
|
| (default) |
|
|
| |
P5 | Low temo limit 64 | o | F (default) | Low temp limit 67 | o | F | ||||
|
| |||||||||
P6 | Hi temp limit 88 | o | F (default) | Hi temp limit 84 | o | F | ||||
|
|
First Operations, LP. - P.O. BOX 270969 - Dallas, Texas 75227 - Ph. (214)