Bryant TSTATBBPCM01-A instruction manual Smart Recovery Heating Mode Only, Troubleshooting, Ð6Ð

Page 6

been restored (plus 15 seconds). If the line voltage is com- pletely interrupted, the thermostat display will immediately go blank.

X. SMART RECOVERY (Heating Mode Only)

The thermostat has 2 programmed schedule modes, normal occupied mode and setback mode (a time when the space is

unoccupied). The Smart Recovery function begins 1.5 hours before the scheduled occupied mode and gradually adjusts room temperature so the temperature is at the occupied mode set point when the occupied time period begins.

 

TROUBLESHOOTING

 

 

PROBLEM

SOLUTION

LCD display on thermostat not illuminated

Check for 24 vac between R and C at terminal connections. Both R and

 

C must be connected for proper thermostat operation.

``E2'' displayed on thermostat

Brownout condition or voltage is too low to thermostat. Check wiring and

 

check for 24 vac at R and C. The E2 error will clear 15 seconds after

 

acceptable power levels are restored.

``E1'' displayed on thermostat

Temperature sensor reading is out of range. Check the sensor for dam-

 

age. Check sensor wiring. Cycle power to thermostat. If display is not

 

cleared, replace thermostat .

``Clean Filter'' is displayed on thermostat

After the con®gured number of blower operating hours, the Clean Filter

 

message will be displayed. This reminds the owner to replace the ®lter.

 

Press the Reset Filter button to reset the blower operation timer to

 

0 hours.

``--'' displayed on thermostat

If the outdoor thermostat is in error, not connected, or shorted, ``--'' will be

 

displayed. Check outdoor thermostat wiring and replace if necessary.

Cooling will not energize

Select COOL mode. Decrease cooling set point to 10 degrees below

 

room temperature. Simultaneously press Fan and Up buttons to disable

 

timers. Check for 24 vac at Y/Y2 terminal. If present, thermostat is oper-

 

ating correctly and problem is with wiring or equipment. If 24 vac is not

 

present, replace the thermostat.

Heating will not energize

Select HEAT mode. Increase heating set point to 10 degrees above room

 

temperature. Simultaneously press Fan and Up buttons to disable timers.

 

Check for 24 vac at Y/Y2 terminal (for heat pump) or W/W1 terminal (for

 

gas/electric heat unit). If present, thermostat is operating correctly and

 

problem is with wiring or equipment. If 24 vac is not present, replace the

 

thermostat.

Ð6Ð

Image 6
Contents II. SET DIP Switches Safety ConsiderationsInstallation Thermostat Location III. Install ThermostatIV. SET Thermostat Configuration Ð3Ð Thermostat Wiring 542J150 Thermostat Wiring 558G,H240-360 and 580G,H240-360IV. FIFTEEN-MINUTE Staging Timer VI. Select Thermostat Operation SettingsIII. FIFTEEN-MINUTE Cycle Timer VII. Final ChecklistSmart Recovery Heating Mode Only TroubleshootingÐ6Ð Page Packaged Service Training