SETUP MENU
User system settings table (continued)
System setting
Description
Factory default setting (bold) and setting range
LOCKOUT TYPE | Level of lockout (only | OFF: No lockout |
| available if Security is | PARTIAL lockout |
| enabled) | FULL lockout |
MODE LOCKOUT | System mode lockout | OFF: No lockout |
| setting (only available in | FULL: no system mode changes allowed |
| partial lockout) |
|
|
|
|
FAN LOCKOUT | Fan mode lockout setting | OFF: No lockout |
| (only available in partial | TIMED: changes revert after temporary change period |
| lockout) | FULL: no fan mode changes allowed |
SETPOINT LOCKOUT | Setpoint lockout setting | OFF: No lockout |
| (only available in partial | |
| lockout) | |
|
| TIME AND RANGE: set by max setpoint lockout and temporary change period |
|
| FULL: no setpoint changes allowed |
|
|
|
MAX SETPOINT | Setpoint range limit | ±5° F or C, ±5% RH |
CHANGE IN LOCKOUT | for temperature and | OFF to ±20° F or C, OFF to ±20% RH |
| humidity adjustments |
|
| (only available in partial |
|
| lockout) |
|
TEMPORARY CHANGE | 60 MINUTES | |
PERIOD | temporary change period | 0 to 255 MINUTES |
| (only available in partial |
|
| lockout) |
|