Aube Technologies TH146-P-2H1C manual Configuration Menu, Hvac

Page 8

Configuration Menu

Item

HP

HVAC

Parameters

Display

Options

Default

Description

 

 

 

 

 

 

 

 

1

Time format

 

12 Hr / 24

24 Hr

Select the time display format.

 

Hr

 

 

 

 

 

 

 

 

 

 

 

 

 

 

• On: Heating or cooling starts in advance (as determined by the con-

 

 

 

 

 

 

 

troller) so that the desired temperature is attained at the set times.

2

Early Start

 

On / OF

OF

• OF (Off): Heating or cooling starts at the set times.

 

NOTE: Early Start applies for periods 1 and 3 (P1 and P3) only. When

 

 

 

 

 

 

 

 

 

 

 

 

 

 

this feature is enabled, heating or cooling will start in advance of the set

 

 

 

 

 

 

 

time for P1 and P3 but will start at the set time for P2 and P4.

• OF (Off): The function is deactivated.

 

Automatic daylight

 

 

• 1 : The controller switches to daylight savings time on the first Sunday

3

OF / 1 / 2

OF

of April and to normal time on the last Sunday of October.

savings adjustment

 

 

 

 

 

• 2 : The controller switches to daylight savings time on the second

 

 

 

 

 

 

 

 

 

 

 

 

Sunday of March and to normal time on the first Sunday of November.

4

Temperature format

°C / °F

°C

Select the temperature display format.

 

 

 

 

 

 

 

 

 

 

-30 to 10°C

-10°C

Set the bP L limit (see section 4.2).

5

 

Balance point low

NOTE: Lower bP L below its minimum (- -) if you do not wish to use this

 

(-22 to 50°F)

(14°F)

 

 

 

 

function.

 

 

 

 

 

 

 

 

 

-5 to 30°C

5°C

Set the bP H limit (see section 4.2).

6

 

Balance point high

NOTE: Raise bP H above its maximum (- -) if you do not wish to use this

 

(23 to 86°F)

(41°F)

 

 

 

 

function.

 

 

 

 

 

 

 

 

 

-10 to 15°C

10°C

Set the defrost point temperature (see section 4.3).

7

 

Defrost point

NOTE: Raise the defrost point above its maximum (- -) if you do not wish

 

(14 to 59°F)

(50°F)

 

 

 

 

to use this function.

 

 

 

 

 

 

 

 

 

 

 

 

Set according to the type of heat pump installation (see section 4.4).

 

 

 

 

 

 

• Ad (add-on): Use this setting when the indoor coils are located down-

 

 

 

 

 

stream of the auxiliary heat source. This is generally the case for add-

8

 

Installation type

Ad / nr

Ad

on installations.

 

 

 

 

 

 

• nr (normal): Select this setting when the indoor coils are located

 

 

 

 

 

 

upstream of the auxiliary heat source. This is generally the case for

 

 

 

 

 

 

new installations.

9

 

Auxiliary

5 to 90 min.

30 min.

Set the interstage delay for the auxiliary stage (see section 4.5).

 

interstage delay

 

 

 

 

 

 

 

 

Low temperature

-10 to 20°C

5°C

Set the low temperature limit of the plenum (see section 4.6).

10

 

NOTE: This function is not used if you lower LLMT below its minimum

 

limit

(14 to 68°F)

(41°F)

 

 

 

(- -) or if the plenum sensor is not connected to the controller.

 

 

 

 

 

 

 

 

High temperature

30 to 90°C

70°C

Set the high temperature limit of the plenum (see section 4.6).

11

 

(86 to

NOTE: This function is not used if you raise HLMT above its maximum (-

 

limit

(158°F)

 

 

 

194°F)

-) or if the plenum temperature sensor is not connected to the controller.

 

 

 

 

 

 

 

 

 

 

 

Select the number of heating/cooling cycles per hour. For optimal heating

12

Cycles per hour

2 to 6

4

control, use the setting that matches your system as follows: 3=20 min

(hot water, 90%+ high-efficiency furnace), 4=15 min (gas or oil), 5=12 min

 

 

 

 

 

 

 

 

 

 

 

 

(gas or oil), 6=10 min (electric).

 

 

 

 

 

 

This setting determines the fan operation in automatic mode when the

 

 

 

 

 

 

system is in heating mode.

 

 

 

 

 

 

• EL (electric heating): The fan starts and stops at the same time as

13

 

Heat type

GA / EL

EL

heating.

 

• GA (gas or oil heating): The fan starts when the temperature inside

 

 

 

 

 

 

the plenum rises above the Fan Limit (see item 14) and stops when

 

 

 

 

 

 

the temperature drops 12°C below the Fan Limit. Note: The fan will

 

 

 

 

 

 

not start if the plenum temperature sensor is not connected to the con-

 

 

 

 

 

 

troller.

 

 

 

 

38 to 90°C

 

This parameter is available only when gas heating is selected (see item 13).

 

 

 

80°C

WARNING: FLMT can be used in parallel with an UL353-approved

14

 

Fan limit

(100 to

 

(176°F)

device but they do not replace such device.

 

 

 

 

194°F)

 

 

 

 

 

NOTE: The fan will not start if you raise FLMT above its maximum (--).

 

 

 

 

 

 

15

Smart Fan

On / OF

OF

On: Smart Fan is On (see section 4.7).

OF: Smart Fan is Off.

 

 

 

 

 

 

16

Temperature

0 to 9°C

0°C

Set the amount of temperature setback when the controller is placed in

setback

(0 to 16°F)

(0°F)

Unoccupied mode (see section 6.4).

 

 

 

 

 

 

 

 

 

• Co (conventional): The humidifier will operate if the humidity is too

 

 

 

 

 

 

low. If the fan is not already On, it will turn On at the same time as the

 

 

 

Humidifier

 

 

humidifier.

17

Co / HE / Fn

Fn

• HE (heat): The humidifier can operate only when heating is activated.

operating mode

 

 

 

 

 

• Fn (fan): The humidifier can operate as long as the fan is running,

 

 

 

 

 

 

 

 

 

 

 

 

whether heating is activated or not.

 

 

 

 

 

 

NOTE: The humidifier is disabled when cooling is activated.

Note: Only items 1 to 4 are available when the controller is placed in user mode (SW1-1 switch).

TH146-P-2H1C

400-280-014-A

5/23/07

8/11

Image 8
Contents Installation IntroductionConfiguration Principles of Operation Wiring Tables Connect the humidifier between the H terminals dry contactWiring Diagram 2H1C Heat Pump New Installation Wiring Diagram 2H1C Heat Pump Add-on Installation Wiring Diagram 1H1C Hvac Configuration Menu HvacGeneral Setting Temperature SettingTemperature Adjustment Unoccupied ModeHumidity Setting WarrantyTechnical Specifications Humidity Adjustment

TH146-P-2H1C specifications

Aube Technologies, a renowned leader in temperature control and energy management solutions, has developed the TH146-P-2H1C model, a programmable thermostat designed to enhance user comfort and streamline energy consumption. This advanced thermostat is particularly acclaimed for its versatility and intelligent features, making it an ideal choice for both residential and commercial applications.

One of the main features of the TH146-P-2H1C is its ability to control heating systems efficiently. It supports various heating types, including electric baseboards, fan-forced heaters, and conventional heating systems, making it a flexible option for different environments. The thermostat offers simple programming options, allowing users to set specific temperatures for different times of the day and days of the week. This level of customization helps to optimize energy usage, leading to potential cost savings on heating bills.

In terms of technology, the TH146-P-2H1C incorporates an intuitive interface with a large, easy-to-read display. The user-friendly design facilitates straightforward programming and real-time temperature monitoring. It utilizes advanced temperature sensors to ensure accurate readings, adapting to the home or building’s unique heating needs. The thermostat also features a "hold" function, which allows users to maintain a specific temperature for an extended period, providing increased flexibility during unexpected schedule changes.

Another key characteristic of the TH146-P-2H1C is its energy-saving capabilities. It includes a built-in energy monitoring feature, enabling users to track their energy consumption over time. This transparency empowers homeowners and facility managers to make informed decisions about their heating practices, further promoting energy efficiency. The device also complies with modern energy standards, making it an environmentally friendly choice.

Security is another aspect that Aube Technologies emphasizes with this model. The TH146-P-2H1C includes a locking feature that prevents tampering, ensuring consistent settings and preventing unauthorized adjustments, which is particularly important in commercial settings.

Overall, the Aube Technologies TH146-P-2H1C thermostat represents a blend of functionality, energy efficiency, and user-friendly design. With its robust features and commitment to precise temperature control, it stands out as a compelling choice for those looking to enhance their heating systems while contributing to energy conservation efforts. Whether for personal residences or commercial spaces, the TH146-P-2H1C is poised to deliver comfort and reliability.