14. Installation

14.4 Connecting Pipings and the cable to Outdoor unit

14.4.1 Connecting the pipings to the Outdoor unit

1. While installing pipes, you must use the connector.

Indoor Units

 

Gas

 

Liquid

 

 

 

 

 

 

 

 

A

 

B

A

 

B

18k, 24k

Ø9.52Ø12.7

Not necessary

 

 

 

 

 

 

 

A B

*Connecting pipe size

Indoor Units

Gas side

Liquid side

7k

Ø9.52(3/8)

Ø6.35(1/4)

9k

Ø9.52(3/8)

Ø6.35(1/4)

12k

Ø9.52(3/8)

Ø6.35(1/4)

18k

Ø12.7(1/2)

Ø6.35(1/4)

24k

Ø12.7(1/2)

Ø6.35(1/4)

 

 

 

2.Align the center of the pipings and tighten the flare nut by hand

Connector

3.Finally, tighten the flare nut with torque wrench until the wrench clicks.

When tightening the flare nut with torque wrench, ensure the direction for tightening follows the arrow on the wrench.

Outdoor unit

A-UNIT

 

 

Gas side piping

 

B-UNIT

 

Liquid side piping

Torque wrench

14.4.2 Connect the cable

Connecting the cable to the Indoor unit.

Connect the cable to the indoor unit by connecting the wires to the terminals on the control board indi- vidually according to the outdoor unit connection. (Ensure that the color of the wires of the outdoor unit and the terminal No. are the same as those of the indoor unit.)

The earth wire should be longer than the common wires. The circuit diagram is not subject to change without notice.

When installing, refer to the circuit diagram of indoor & outdoor unit. Indoor connection circuit is behind the front panel & outdoor connection circuit is inside the control cover.

CAUTION:

The circuit diagram is not subject to change without notice.

Be sure to connect wires according to the wiring diagram.

Connect the wires firmly, so that not to be pulled out easily.

Connect the wires according to color codes as referred in the wiring diagram.

72MPS Variable Multi Split System(50Hz, R410A)

Image 73
Contents Free Joint, 50Hz, R410A LM50 2004-E1LG Electronics Inc General DescriptionAir Conditioning Division MPS Variable Multi Split System50Hz, R410A Table of Contents MPS Variable Multi Split System50Hz, R410A Part Power Consumption Comparison Features & BenefitBasic Principle of MPS Variable Control What is Carbon Nano Ball? Auto Cleaning SystemAir Purifying System Triple Deodorizing FilterUltra-Slim designDepth 129mm Dimensional Cooling SystemAir Flow Control ART Cool Time Delay Safety function LCD Wireless RemoconEnvironment Friendly Refrigerant Jet CoolMPS Variable Multi Split System50Hz, R410A MPS Variable Multi-Split System External wiring procedure Power SupplyIndoor Units Model Number NomenclatureOutdoor Units Example of System Outline of SystemCombination of Indoor and Outdoor Unit Wall Mounted External Appearance of Indoor UnitsAMNH-AP List of FunctionsCooling Only SpecificationsAMNH076LQL0 Heat PumpIC-9625LGSY Motor Input 1526 1290 2175 Oil Type Cooling Only Combination TableCooling 1 A2UC146FA04 A4UC306FA0 Heating Heat Pump1 A2UH146FA0 2 A2UH186FA03 A3UH216FA0 4 A4UH306FA0 1310 11000 AMNC-LQ/LR/LT, AMNH-LQ/LR/LT Dimensional DrawingsAMNC-AP, AMNH-AP Outdoor Units A2UC146FA0, A2UH146FA0 A2UC186FA0, A2UH186FA0 A3UC216FA0, A3UH216FA0 A4UC306FA0, A4UH306FA0 Indoor Unit Wiring DiagramsWall Mounted AC PWB ASM DC PWB ASM ART Cool TypeA2UC146FA0 Outdoor UnitA2UC186FA0 Outdoor Wiring DiagramMain PWB Assy A3UC216FA0A4UC306FA0 A2UH146FA0 Main PWB Assy A2UH186FA0A3UH216FA0 A4UH306FA0 Cooling Only Piping DiagramsHeat Pump Outdoor Unit LEV-C Outdoor Unit LEV-C Capacity Table 10.3 A3UC216FA0 Cooling Capacity Capacity Table10.4 A4UC306FA0 Cooling Capacity 12+12 +7+7+7 Heating Capacity Heat Pump10.6 A2UH186FA0 Cooling Capacity Capacity Table 10.7 A3UH216FA0 Cooling Capacity Capacity Table 10.8 A4UH306FA0 Cooling Capacity 12+12 CDB 10.46 11.54 10.80 11.92 Range Operation LimitsWall Mounted Type Air Velocity and Temperature DistributionsReference Data7k Btu/h Model Cooling HeatingSound Pressure Level Sound LevelsAMNC/H096AP*1 A4UC/H306FA0 A2UC/H146FA0 A2UC/H186FA0 A3UC/H216FA0 Piping Length & Refrigerant Charge Installation Refrigerant Charge Maximun allowable level and piping lengthWall Mounted Type Select the best locationIndoor Unit Outdoor Unit Settlement of outdoor unitConnecting the cable to the Indoor unit Connecting Pipings and the cable to Outdoor unitConnecting the pipings to the Outdoor unit Connect the cableOutdoor unit Connecting the cable to the Outdoor unitInstallation Drain pipe gradient and support Drain Pipe WorkDrain trap Wireless LCD Remote Controller Function of Remote ControllerOperation Mode No A20428F