Enduser settings
With
In addition, following can be entered by the enduser:
–Room temperature setpoints for normal heating, reduced heating and frost protec- tion/holidays
–
–Operating mode
–Time of day and date
Temperature acquisition | – | Flow temperature: with one or two (averaging) sensors |
| – Outside temperature: with Ni or NTC sensor; the RVL469 identifies the type of sensor | |
|
| used; with interlinked controllers, it is also possible to define the source of the outside |
|
| temperature |
| – Room temperature: with a room temperature sensor or a room unit, or both (averaging) | |
Space heating | • | The room temperature is included in the control. It can be acquired with a sensor or |
|
| simulated by a room model with an adjustable building time constant. When using a |
|
| sensor, the effect on the control can be adjusted. |
|
| It is also possible to limit the maximum room temperature. |
| • | The heating is switched on and off depending on demand (ECO function). It is swit- |
|
| ched off when the amount of heat stored by the building mass is sufficient to maintain |
|
| the required room temperature. In that case, the controller takes into account the de- |
|
| velopment of the room temperature and the building's heat storage capacity. It is pos- |
|
| sible to set two heating limits, one for normal heating and one for reduced heating. |
| • | The control is optimized. Switching on, heating up and shutting down are controlled |
|
| such that, during occupancy times, the required room temperature is always main- |
|
| tained. |
|
| At the end of each occupancy period, the heating will be shut down (circulating pump) |
|
| until the room temperature setpoint for the |
|
| back, can be disabled). During heating up, the room temperature setpoint can be |
|
| boosted (boost heating). It is possible to set maximum limits for the heating up time |
|
| and for early shutdown. |
| ||
| perature control. |
controlled via the regulating unit (control or slipper valve).
Minimum and maximum limitation of the flow temperature as well as maximum limitation of the rate of setpoint rise are adjustable.
Minimum limitation of return temperature
Locking functions
Time switch
Remote control
Minimum limitation of the return temperature acts with both
On the software side, all settings can be locked to prevent unauthorized readjustments.
–The RVL469 has one
–For entering a maximum of eight holiday periods, the RVL469 is equipped with a yearly time switch featuring automatic
–Changeover of operating mode with the QAW50 room unit
–Overriding the major controller functions with the QAW70 room unit
–Selection of another (programmable) operating mode with an external contact
–Preselection of a fixed flow temperature setpoint with an external contact. Type of setpoint (fixed or minimum) and flow temperature can be selected
Siemens Building Technologies | CE1N2527E / 04.03.1999 |
Landis & Staefa Division | 3/8 |