State Industries GS6 50 YBRT Series 200 All Air from Inside the Building, All Air from Outdoors

Page 12

12” MAXIMUM

 

 

 

CLOSET

 

 

 

PERMANENT

 

OR

 

OTHER

OPENINGS TO

 

CONFINED

THE OUTSIDE OR

 

SPACE

ADDITIONAL

 

 

ROOMS WITHIN

 

 

THE BUILDING

 

 

12” MAXIMUM

FIGURE 4.

All Air from Inside the Building

When additional air is to be provided to the confined area from additional room(s) within the building, the total volume of the room(s) must be of sufficient size to properly provide the necessary amount of fresh air to the water heater and other gas utilization equipment in the area. If you are unsure that the structure meets this requirement, contact your local gas utility company or other qualified agency for a safety inspection.

Each of the two openings shall have a minimum free area of 1 square inch per 1,000 BTUH of the total input rating of all gas utilization equipment in the confined area, but not less than 100 square inches (Figure 5).

CONFINED

SPACE

PERMANENT

OPENINGS

1 SQUARE

INCH/1000

BTUH

(MINIMUM

100 SQ. IN.)

FIGURE 5.

All Air from Outdoors

Outdoor fresh air can be provided to a confined area either directly or by the use of vertical and horizontal ducts. The

fresh air can be taken from the outdoors or from crawl or attic spaces that freely communicate with the outdoors. Attic or crawl spaces cannot be closed and must be properly ventilated to the outside.

Ductwork must be of the same cross-sectional area as the free area of the opening to which they connect. The minimum dimension of rectangular air ducts cannot be less than three inches.

The size of each of the two openings is determined by the method in which the air is to be provided. Refer to Table 4 to calculate the minimum free area for each opening. Figures 6, 7, 8A and 8B are typical examples of each method.

Louvers and Grilles

In calculating free area for ventilation and combustion air supply openings, consideration must be given to the blocking effect of protection louvers, grilles, and screens. These devices can reduce airflow, which in turn may require larger openings to achieve the required minimum free area. Screens must not be smaller than 1/4” mesh. If the free area through a particular design of louver or grille is known, it should be used in calculating the specified free area of the opening. If the design and free area are not known, it can be assumed that most wood louvers will allow 20 - 25% of free area while metal louvers and grilles will allow 60 - 75% of free area.

Louvers and grilles must be locked open or interconnected with the equipment so that they are opened automatically during equipment operation.

Keep louvers and grilles clean and free of debris or other obstructions.

TABLE 4

Minimum Free Area of Permanent Openings for Ventilation and Combustion Air Supply - All Air from Outdoors Only.

Based on total BTUH input rating for all utilizing equipment within the confined space.

 

Minimum Free Area

 

Opening Source

Per Opening (sq. in.)

Reference Drawing

*Direct to outdoors

1 sq. in, per 4000 BTUH

Figure 6

Vertical Ducts

1 sq. in, per 4000 BTUH

Figure 7

Horizontal Ducts

1 sq. in, per 2000 BTUH

Figure 8A

Single Opening

1 sq. in, per 3000 BTUH

Figure 8B

Example: A water heater with an input rating of 50,000 BTUH using horizontal ducts would require each opening to have a minimum free area of 25 square inches.

Minimum free area = 50,000 BTUH x 1 sq. in. / 2000 BTUH = 25 sq. in.

*These openings connect directly with the outdoors through a ventilated attic, a ventilated crawl space, or through an outside wall.

Consult the local codes of your area for specific ventilation and combustion air requirements.

12

Image 12
Contents Fvir GAS Water Heater Table of Contents Safe INSTALLATION, USE and Service Safety PrecautionsFire or Explosion Harzard Typical Installation GET to Know Your Water Heater GAS ModelsInstalling Your GAS Water Heater Unpacking the Water Heater Excessive Weight HazardImportant Information About This Water Heater Consumer InformationLocation Requirements Site LocationCarbon Monoxide Poisoning Hazard Fire or Explosion HazardClearances and Accessibility State of California Gas Pressure Testing GAS Supply Gas Requirements Gas PipingLP Gas Only Explosion HazardCombustion AIR & Ventilation Unconfined SpaceConfined Space Minimum Btuh InputAll Air from Inside the Building All Air from OutdoorsLouvers and Grilles Draft Hood Installation Vent Pipe SystemVent Connectors Vent Pipe SizeChimney Connection Vertical Exhaust Gas VentPiping Installation Water System PipingClosed System/Thermal Expansion Temperature and Pressure Relief Valve Explosion HarzardRelief Valve and Pipe Insulation Some Models Combination Space Heating/Potable Water SystemSolar Installation Installation Checklist Important Information about this Water HeaterCombustion Air Supply and Ventilation Operating Your Water Heater Lighting InstructionsChecking the Draft Burn HazardWater Temperature Regulation Burner FlamesEmergency Shut Down White Rodgers ValvesSafety Shut-off Operational ConditionsCondensation Water Heater SoundsRoutine Preventive Maintenance Draining and FlushingAnode Rod/Water Odor Maintenance of Your Water Heater Replacement PartsRemoving the Manifold/Burner Assembly Removing the Burner from the Manifold/ Burner AssemblyReplacing the Pilot/ Pilot Tube Assembly Replacing the ThermocoupleExternal Inspection & Cleaning of the Base-Ring Filter Cleaning the Combustion Chamber and Flame-arrestorReplacing the Manifold/Burner Assembly Testing the Igniter System Piezoelectric Igniter SystemRemoving and Replacing the Gas Control Valve/Thermostat Removing the Gas ValveFvir System Operational Checklist Troubleshooting ChartReplacing the Gas Valve Turn temperature dial to desired setting Pilot Light Troubleshooting Flowchart YESRepair Parts List Repair Parts IllustrationListed Parts Kits and Illustrations Page Limited Residential GAS Warranty YearImportant Information