Desa S26NT installation manual Checking GAS Connections, Pressure Testing Gas Supply Piping System

Page 9

OWNER’S MANUAL

INSTALLATION

Continued

CHECKING GAS

CONNECTIONS

WARNING: Test all gas pip- ing and connections for leaks after installing or servicing. Cor- rect all leaks at once.

WARNING: Never use an open flame to check for a leak. Apply a mixture of liquid soap and water to all joints. Bubbles forming show a leak. Correct all leaks at once.

Pressure Testing Gas Supply Piping System

Test Pressures In Excess Of 1/2 PSIG (3.5 kPa)

Test Pressures Equal To or Less Than 1/2 PSIG (3.5 kPa)

1.Close equipment shutoff valve (see Fig- ure 7).

2.Pressurize supply piping system by ei- ther using compressed air or opening main gas valve located on or near gas meter.

3.Check all joints from gas meter to equipment shutoff valve (see Figure 8). Apply mixture of liquid soap and water to gas joints. Bubbles forming show a leak.

4.Correct all leaks at once.

Open

Equipment

Shutoff

Valve

CO losed

POS

Figure 7- Equipment Shutoff Valve

Pressure Testing Heater Gas Connections

1.Open equipment shutoff valve (see Fig- ure 7).

2.Open main gas valve located on or near gas meter.

3.Make sure control knob of heater is in the OFF position.

4.Check all joints from equipment shutoff valve to control valve (see Figure 8). Apply mixture of liquid soap and wa- ter to gas joints. Bubbles forming show a leak.

5.Correct all leaks at once.

6.Light heater (see Operating Heater, pages 11 and 12). Check all other in- ternal joints for leaks.

7.Turn off heater (see To Turn Off Gas to Appliance, page 12).

1.Disconnect appliance with its appliance main gas valve (control valve) and equip- ment shutoff valve from gas supply pip- ing system. Pressures in excess of 1/2 psig will damage heater regulator.

2.Cap off open end of gas pipe where equipment shutoff valve was connected.

3.Pressurize supply piping system by ei- ther using compressed air or opening main gas valve located on or near gas meter.

4.Check all joints of gas supply piping system. Apply mixture of liquid soap and water to gas joints. Bubbles form- ing show a leak.

5.Correct all leaks at once.

6.Reconnect heater and equipment shutoff valve to gas supply. Check re- connected fittings for leaks.

Equipment Shutoff

Valve

Gas Meter

Control Valve Location

Figure 8 - Checking Gas Joints

Continued

105683

9

For more information, visit www.desatech.com

Image 9
Contents What to do if YOU Smell GAS OWNER’S Operation and Installation ManualVENT-FREE Natural GAS Pedestal Stove Safety InformationProduct Identification Product FeaturesLocal Codes UnpackingProviding Adequate Ventilation AIR for Combustion and VentilationUnusually Tight Construction Confined and Unconfined SpaceAIR for Combustion Ventilation Determining FRESH-AIR Flow for Heater LocationDetermining if You Have a Confined or Unconfined Space Ventilation AIR Ventilation Air From Inside BuildingVentilation Air From Outdoors Check GAS Type InstallationClearances to Combustibles Vent-Free Operation OnlyInstallation Items Needed Connecting to GAS SupplyPressure Testing Gas Supply Piping System Pressure Testing Heater Gas ConnectionsChecking GAS Connections Installing Blower Accessory GA3750 Installing LogsOperating Heater For Your Safety Read Before LightingInspecting Burners Cleaning and Maintenance Observed Problem Possible Cause Remedy TroubleshootingNance, Top Service Hints SpecificationsTechnical Service Parts CentralsS26NT Illustrated Parts BreakdownKEY Part Number Description QTY Parts ListVENT-FREE Natural GAS Pedestal Stove KEY Description QTY Accessories Replacement Parts105683 International Limited Warranty VENT-FREE Natural GAS Pedestal Stove