Desa CDR3924NT installation manual Ventilation AIR, Ventilation Air From Inside Building

Page 7

AIR FOR COMBUSTION

AND VENTILATION

Continued

A.

Rework worksheet, adding the space of an adjoin-

 

ing room. If the extra space provides an unconfined

 

space, remove door to adjoining room or add

 

ventilation grills between rooms. See Ventilation

 

Air From Inside Building.

B.

Vent room directly to the outdoors. See Ventila-

 

tion Air From Outdoors, page 7.

Ventilation

 

Grills

 

Into Adjoining

Or

Room,

Remove

Option 1

Door into

 

 

Adjoining

 

Room,

 

Option

 

3

12"

Ventilation Grills

Into Adjoining Room,

Option 2

C. Install a lower Btu/Hr heater, if lower Btu/Hr size

makes room unconfined.

If the actual Btu/Hr used is less than the maximum Btu/Hr the space can support, the space is an un- confined space. You will need no additional fresh air ventilation.

WARNING:Iftheareainwhich the heater may be operated is smaller than that defined as an unconfined space or if the building is of unusually tight construction, provide adequate combustion and ventilation air by one of the methods described in the National Fuel Gas Code, ANSI Z223.1/NFPA54 Section 5.3 or applicable local codes.

VENTILATION AIR

Ventilation Air From Inside Building

This fresh air would come from an adjoining un- confined space. When ventilating to an adjoining unconfined space, you must provide two perma- nent openings: one within 12" of the ceiling and one within 12" of the floor on the wall connecting the two spaces (see options 1 and 2, Figure 2). You can also remove door into adjoining room (see option 3, Figure 2). Follow the National Fuel Gas Code, ANSI Z223.1/NFPA 54, Section 5.3, Air for Combustion and Ventilation for required size of ventilation grills or ducts.

12"

Figure 2 - Ventilation Air from Inside

Building

Ventilation Air From Outdoors

Provide extra fresh air by using ventilation grills or ducts. You must provide two permanent openings: one within 12" of the ceiling and one within 12" of the floor. Connect these items directly to the outdoors or spaces open to the outdoors. These spaces include attics and crawl spaces. Follow the National Fuel Gas Code, ANSI Z223.1/NFPA 54, Section 5.3, Air for Combustion and Ventilation for required size of ventilation grills or ducts.

IMPORTANT: Do not provide openings for inlet or outlet air into attic if attic has a thermostat- controlled power vent. Heated air entering the attic will activate the power vent.

 

Outlet

Ventilated

 

Attic

 

Air

 

 

Outlet

 

 

Air

 

To Attic

 

 

 

 

To

 

 

Crawl

Inlet

 

Space

 

 

Air

 

 

 

Inlet Air

Ventilated

 

Crawl Space

 

 

Figure 3 - Ventila tion Air from Outdoors

113183-01B

www.desatech.com

7

Image 7
Contents Thermostat Models CDR3924NT and CDR3924PT What to do if YOU Smell GASTable of Contents Safety Information Local Codes Product Identification Product FeaturesConfined and Unconfined Space AIR for Combustion VentilationDetermining FRESH-AIR Flow for Heater Location Unusually Tight ConstructionVentilation Air From Inside Building Ventilation AIRVentilation Air From Outdoors Check GAS Type InstallationWidth Installation and Clearances for VENT-FREE OperationLog RearDetermining Minimum Mantel Clearance Determining Minimum Mantel Clearance When Using a HoodMantel Clearances Floor ClearancesInstallation Items Needed Installing Heater Base AssemblyExternal Regulator With Vent Pointing Down Connecting to GAS SupplyTest Pressures In Excess Of 1/2 Psig 3.5 kPa Checking GAS ConnectionsPropane/LP From Natural From GasTest Pressures Equal To or Less Than 1/2 Psig 3.5 kPa Installing LogsAdding Lava Rock Attaching Grate to Base AssemblyOperating Heater For Your Safety Read Before LightingLighting Instructions To Turn OFF GAS To Appliance Manual Lighting ProcedureThermostat Control Operation Burner Flame Patterns Technical ServiceInspecting Burners Pilot Flame PatternBurner Injector Holders and Pilot AIR Inlet Holes Cleaning MaintenanceLogs Observed Problem Possible Cause Remedy TroubleshootingMaintenance, Cold Minute Air in gas line Operate burners until air is Gas leak. See Warning For Masonry and FACTORY- Built Metal Fireplace Optional Positioning Thermostat Sensing BulbAccessories SpecificationsReplacement Parts Service HintsModels CDR3924PT and CDR3924NT Illustrated Parts BreakdownParts List Keep this Warranty Warranty InformationLimited Warranty Comfort Glow VENT-FREE GAS LOG Heaters