Bradford-White Corp B4 warranty Site Location, Installation Information, Outdoor Installation

Page 5

Internet Version for Reference Only

Copper Brute B4 Volume Water Heaters

Page 5

 

 

 

 

e.Slide the adapter plate over the bottom of the stack extension as shown in Figure 5. Fit the stack extension down over the flue transition ring. Seat the adapter plate on the top assembly and secure it with two screws (see Figure 6).

f.Indoor models, size 175 and 250 only, require an adapter cable (included with product). The cable connects the blocked vent safety switch (BVSS) on the bell of the external draft hood to the 6-position Molex plug on the side of the unit (see Figure 7). Refer to instruction sheet included with cable.

2.3Site Location

2.3.1 Installation Information

WARNING

Improper installation or maintenance can cause nausea or asphyxiation from carbon monoxide in flue gases which could result in severe injury, property damage, or death.

Avoid placing the heater in locations where it can be damaged by water or condensate leakage. If this is not possible, provide a suitable drain pan to catch and divert any leakage. The pan must not block natural flow of air around the heater.

Locate the heater to provide adequate clearance on all sides for inspection, service and to provide adequate air circulation for proper operation.

Locate the heater so the clearances from combustible surfaces shown in Table 1 and Figure 8 are met.

Locate the heater on a waterproof floor with a floor drain and a 6 inch (152 mm) minimum curb on all four sides to protect the building if heater repairs are needed.

Clearance from:

Indoors

Outdoors

inch

mm

inch

mm

 

 

 

 

Top

37

940

Unobstructed

Water conn. side

12

305

Unobstructed

Opposite side

6

152

6

152

Front

Alcove

Unobstructed

Rear

6

152

6

152

Vent*

6

152

 

Flooring

Combustible

Combustible

Service clearance = 36 inches (914mm) at front of heater, and 18 inches (457mm) at water connection side.

*1" (25mm) if double wall vent is used.

Table 1. Minimum Boiler Clearances from Combustible Surfaces.

Closet Installation

Room Installation

(unacceptable)

(acceptable)

A closet is any 4 sided enclosure

A room is any enclosure which is

which is less than 16* times the

at least 16* times greater than the

total volume of all the gas fired ap-

total volume of all the gas fired ap-

pliances within the enclosure.

pliances within the enclosure

Alcove Installation

(acceptable)

An alcove suitable for the installa- tion of a heater is a restricted sec- tion of a room not separated from the room by a door or partition and which meets the minimum clear- ances specified in this manual.

*When the ceiling height exceeds 8 feet, you are only allowed to con- sider 8 feet when calculating the total volume of the enclosure.

Figure 8. Alcove installation.

2.3.2 Outdoor Installation

Caution

Outdoor installations are not recommended in areas where the danger of snow blockage exists. Copper Brute heaters can be installed in the standard low- profile, grate top configuration as received from the factory, or with an optional vent cap.

Locate the heater in an open, unroofed area. Do not locate the heater below or adjacent to any doors, windows, louvers, grills, etc., which connect in any way with an inhabited area of a building, even though the access might be through another structure such as a garage or utility room (see Figure 9 and Table 1). There must be a minimum of 4 feet (1.22

m)horizontally and vertically between the heater and any door, window, or gravity inlet to a building (see Figure 10).

If the heater is installed close to a structure, protect it from rain water runoff with rain gutters on the roof or other measures. Do not locate the heater near sprinkler systems that could spray water on it.

Avoid locations where wind deflection off nearby structures might cause wind loading and downdraft conditions. Where downdraft conditions exist, locate the heater at least 3 feet (0.91 m) from the structure.

Image 5
Contents Copper Brute Table of Contents General Information WarrantyIntroduction Technical AssistanceField Assembly Installation InstructionsSite Location Installation InformationOutdoor Installation Combustion and Ventilation Air Supply Flooring Typical InstallationOutdoor Air Supply MethodIndoor Air Supply Exhaust Fans or VentsWater Flow Venting of Combustion ProductsGeneral Information Reversible Water ConnectionsHeat exchanger reversal Front Freeze Protection Water ChemistryWater Hardness Pump RequirementsCold water application Hot water supply with vertical tank Pressure Buildup in Water System Storage Tank InstallationPressure Relief Valve Water PressureGeneral Instructions Gas Supply and PipingThermal Circulation of Hot Water Operating Instructions Electrical WiringCombined Space Heating/Potable Water Heating Systems Normal Operating SequenceIgnition System no Sizes ON/OFF with EM2 18BRADFORD White Ignition System no Sizes ON/OFF with EM2ON/OFF with Em2 Ignition System no SizesPump W Relay LOW Water CUT-OFF Optional Power Switch Remote Water Heater Temperature Control Start-Up ProcedureSetting the Temperature Controls Internal Water Heater Temperature Control Hi-Limit Switch CheckoutShut-Down Procedure General Instructions MaintenanceReplacement of Gas Controls Gas valve/burner replacement Inspecting the Heat Exchanger Cleaning the Heat ExchangerGas Pressure Tests Electrical TroubleshootingChecking the Main Line Gas Pressure Checking the Manifold Regulated Gas PressureHeater Does Not Come On Testing the TransformerTesting the Manual Reset Hi-Limit Switch Testing the Electrical Power SupplyTesting the Flow Switch Testing the Fusible Link Flame roll-out switchTesting the High Voltage Ignition Lead Testing the FuseTesting the Ignition Control for spark ignition Testing the Safety Shutoff For automatic pilot Testing the Safety Shutoff for standing pilotTesting the Igniter Electrode Testing the Pilot Thermocouple for standing pilotTesting the Terminal Strip/ External Controls Testing for Burner Ignition For standing pilotHeater Will Not Shut Off On-Off Main Burner CyclingBradford White

B4 specifications

Bradford-White Corp B4 is a remarkable water heater that embodies innovation, efficiency, and reliability. This product is designed to meet the stringent demands of both residential and commercial applications, making it a versatile choice for various users.

One of the standout features of the Bradford-White B4 is its high-efficiency operation. With advanced insulation technologies, this water heater minimizes heat loss, allowing it to perform efficiently while conserving energy. This efficiency translates to significant cost savings on utility bills, making the B4 an economical option over its lifespan.

Moreover, the B4 employs a robust and durable construction. Engineered with top-quality materials, it boasts a glass-lined tank that prevents corrosion and extends the longevity of the unit. This durable design ensures that users can rely on their water heater for many years, thus reducing the frequency of replacements and repairs.

The Bradford-White B4 is equipped with state-of-the-art technologies to enhance user convenience. Among these technologies is the ICON System, which features an advanced gas control. This control system allows for precise temperature management and ensures optimal performance. Additionally, the B4 comes with a built-in diagnostic system that provides insight into the operation of the unit, helping users identify potential issues before they escalate.

Another significant characteristic of the B4 is its variety of sizes and configurations. This versatility allows for easy installation in different spaces, whether it be a compact utility room or a larger commercial setup. Available in various capacities, the B4 can efficiently deliver hot water for various needs, catering to families of different sizes or businesses with diverse requirements.

Safety is also a top priority for Bradford-White. The B4 includes safety features such as a temperature and pressure relief valve, which acts as a safeguard against potential malfunctions. This adds an extra layer of peace of mind for users concerned about operational safety.

In summary, the Bradford-White Corp B4 combines high efficiency, durable construction, advanced technologies, versatility, and safety features. This makes it more than just a water heater—it is a dependable solution for ensuring hot water availability for various applications. Whether for a home or a commercial setting, the B4 represents a commitment to quality and performance that users have come to trust.