A.O. Smith 505 Series 100, 705 Series 100, 305 Series 100 manual Outdoor On-Demand Water Heater

Page 20

IMPORTANT!

With electrical power supplied to a on-demand water heater, it will not freeze in enviornments as cold as -30ºF, when protected from direct wind exposure.

In the event of a power failure at temperatures below freezing, the water heater should be drained of all water to prevent freezing damage.

The unit may be drained manually or through the installation of the Optional solenoid valves as shown.

The electrical connections for the two solenoid valves should be tied to the 120 V power terminals provided on the PC Board of the water heater.

When the electrical power to the water heater fails, the cold water supply

drain down solenoid valve opens, allowing the water heater and associated piping to drain. Ensure that you run the drain for the solenoids per local codes.

On-Demand

 

Equipment List

QTY

Outdoor On-Demand

1

Water Heater

 

Vacuum

Breaker

Outdoor

On-Demand

Water Heater

NOTE:

enclosure or recess box and packed with insulation for additional protection.

NOTE:

outside building structure. These are indicated by being above the dashed line.

line should be located inside the building structure.

The vacuum breaker line should be located inside the building structure.

Minimum 3/4" Hot Water

Supply Line

1/4" Minimum

Normally Open

Solenoid Valve

S

3/4" Minimum

Normally Closed

Solenoid Valve

S

Route drain per local codes

Gas Supply Line

Minimum 3/4 " C old W ater

S upply Line

Domestic Hot Water - Optional Freeze Protection

1 Outdoor On-Demand Water Heater

Preferred Piping Installation

Key

3/4" Ball Valve

3/4" Union

Check Valve

Pressure Relief Valve

Pressure Regulator

Circulating Pump

S

Boiler Drain Valve

Solenoid Valve

Mixing Valve

NOTE: This drawing is not intended to describe a complete system and is not a replacement for a pro- fessional engineering drawing. It is intended only as a guide and does not imply compliance with local building code requirements. Confer with local building officials before installation. The Contractor or engineer is to determine the necessary components and configuration of the particular system to be in- stalled. It is the responsibility of the engineer or contractor to ensure that the installation is in accordance with all local building codes.

Drawing Date:

September 07, 2008

Drawing Number:

H-1-E

20

Image 20
Contents On-Demand Water Heater System Design Manual Table of Contents Approvals Installation Water Temperature RegulationConsumer Information Consumer ResponsibilitiesTemperature Time to Produce 2nd & 3rd Site LocationFor Storage Tank System Installation Closed System/Thermal ExpansionTemperature and Pressure Relief Valve Water Quality and Scale Lime DEPOSITED, lb/yrPump Sizing for Circulation Table BTank Water Heaters in a Circulation Loop Additional GuidelinesPump Sizing for Storage Tank Application Pump Flow Requirements100/101 Series 200/201 Series Pressure Loss Curves Key Primary Sub Primary On-Demand Primary Gas Supply Hot Water Supply Line Cold Water Supply Line Outdoor On-Demand Water Heater Sub Gas Supply Line On-Demand Outdoor Water Heaters Electronic Connection For this application On-Demand Water Heater On-Demand Water Heater Primary Tion.On-Demand Water Heater Primary Building Outlets Aquastat Connection Pump Sizing for Storage Tank Application Pump Sizing for Storage Tank On-Demand Commercial Water Heaters Building Circulation Pump Building Hot Water Supply Line On-Demand Equipment List Pump / Aquastat Control Wire Gas Supply Pump Sizing for Storage Tank Application Pump Sizing for MP-01 Page Tennessee Waltz Parkway Ashland, TN