Trane RTHD manual Minimum/Maximum Evaporator Flow Rates Gallons/Minute

Page 17

General Data

Water Flow Rates

 

 

 

 

Minimum/Maximum Evaporator Flow Rates (Gallons/Minute )

 

 

Two Pass

 

Three Pass

 

Four Pass

 

Evaporator

 

 

Nominal

 

 

Nominal

 

 

Nominal

Code

Min

Max

Conn Size (In.)

Min

Max

Conn Size (In.)

Min

Max

Conn Size (In.)

B1

253

1104

8

168

736

6

—-

—-

—-

B2

288

1266

8

192

844

6

—-

—-

—-

C1

320

1412

8

213

941

6

—-

—-

—-

C2

347

1531

8

232

1022

6

—-

—-

—-

D1

415

1812

8

275

1206

8

—-

—-

—-

D2

450

1980

8

300

1320

8

—-

—-

—-

D3

486

2131

8

324

1417

8

—-

—-

—-

D4

351

1542

8

234

1028

8

—-

—-

—-

D5

351

1542

8

234

1028

8

—-

—-

—-

D6

293

1287

8

196

860

8

—-

—-

—-

E1

450

1980

8

300

1320

8

—-

—-

—-

F1

563

2478

10

376

1655

8

—-

—-

—-

F2

604

2667

10

404

1780

8

—-

—-

—-

G1

—-

—-

—-

505

2218

10

379

1666

8

G2

—-

—-

—-

550

2413

10

411

1807

8

G3

—-

—-

—-

622

2732

10

466

2050

8

Notes:

1.Minimum flow rates are based on water only.

2.All water connections are grooved pipe.

Minimum/Maximum Evaporator Flow Rates (Liters/Second)

 

 

Two Pass

 

Three Pass

 

Four Pass

Evaporator

 

 

Nominal

 

 

Nominal

 

 

Nominal

Code

Min

Max

Conn Size (mm)

Min

Max

Conn Size (mm)

Min

Max

Conn Size (mm)

B1

16

70

200

11

46

150

—-

—-

—-

B2

18

80

200

12

53

150

—-

—-

—-

C1

20

89

200

13

59

150

—-

—-

—-

C2

22

97

200

15

65

150

—-

—-

—-

D1

26

114

200

17

76

200

—-

—-

—-

D2

28

125

200

19

83

200

—-

—-

—-

D3

31

134

200

20

89

200

—-

—-

—-

D4

22

97

200

15

65

200

—-

—-

—-

D5

22

97

200

15

65

200

—-

—-

—-

D6

18

81

200

12

54

200

—-

—-

—-

E1

28

125

200

19

83

200

—-

—-

—-

F1

36

156

250

24

104

200

—-

—-

—-

F2

38

168

250

25

112

200

—-

—-

—-

G1

—-

—-

—-

32

140

250

24

105

200

G2

—-

—-

—-

35

152

250

26

114

200

G3

—-

—-

—-

39

172

250

29

129

200

Notes:

1.Minimum flow rates are based on water only.

2.All water connections are grooved pipe.

Minimum/Maximum Condenser Flow Rates (Gallons/Minute)

 

 

Two Pass

 

Condenser

 

 

Nominal

Code

Min

Max

Conn Size (In.)

B1

193

850

6

B2

212

935

6

D1

193

850

6

D2

212

935

6

E1

291

1280

8

E2

316

1390

8

E3

325

1420

8

E4

245

1080

8

E5

206

910

8

F1

375

1650

8

F2

355

1560

8

F3

385

1700

8

G1

444

1960

8

G2

535

2360

8

G3

589

2600

8

Notes:

1.Minimum flow rates are based on water only.

2.All water connections are grooved pipe.

Minimum/Maximum Condenser Flow Rates (Liters/Second)

 

 

Two Pass

 

Condenser

 

 

Nominal

Code

Min

Max

Conn Size (mm)

B1

12

54

150

B2

13

59

150

D1

12

54

150

D2

13

59

150

E1

18

81

200

E2

20

88

200

E3

21

90

200

E4

15

68

200

E5

13

57

200

F1

24

104

200

F2

22

98

200

F3

24

107

200

G1

28

124

200

G2

34

149

200

G3

37

164

200

Notes:

1.Minimum flow rates are based on water only.

2.All water connections are grooved pipe.

RLC-PRC020-EN

17

Image 17
Contents Series R Helical Rotary Liquid Chillers American Standard Inc. All rights reserved IntroductionContents ApplicationVersatility and High Performance Features and BenefitsSimple, Economical Installation State-of-the-Art, Precision Control Reliability and Ease of MaintenanceOperating and Life Cycle Cost-Effectiveness Design capabilities includeOptions Ice Making Control ChilledWater Reset Outdoor Air TemperatureProgrammable Relays Condenser-RegulatingValve ControlControls Additional Display Features IncludeSwift Emergency Response Energy EfficiencyKeeping Operators Informed Variable Evaporator Flow and Short EvaporatorWater Loops Application ConsiderationsAcoustic Considerations Water TreatmentWater Pumps Fouling Factors PerformancePart Load Performance System ConsiderationsElectrical DataTables Unit Performance with Fluid Media OtherThanWaterEvaporator and Condenser Pressure Drop RTH Model NomenclatureDigit 28 Condenser Leaving Water Temperature General Data General DataNominal Data Minimum/Maximum Evaporator Flow Rates Liters/Second Minimum/Maximum Evaporator Flow Rates Gallons/MinuteMinimum/Maximum Condenser Flow Rates Gallons/Minute Minimum/Maximum Condenser Flow Rates Liters/SecondMinimum/Maximum Condenser Flow Rates GPM Minimum/Maximum Evaporator Flow Rates GPMCompressor Motor Electrical Data 50 Hertz Electrical Data ConnectionsCompressor Motor Electrical Data 60 Hertz Electrical Data and Connections Electrical Data and Connections OperatingWeight ShippingWeight Code Lbs Dimensions WeightsShipping and Operating Weights BBB Configuration Front 36 914 mm Back Either End Other End BCD ConfigurationCDE, DDE, EDE Configuration CEF Configuration CFF, DFF, EFF Configuration DGG, EGG Configuration Mechanical Specifications ConversionTable RLC-PRC020-EN File Number PL-RF-RLC-000-PRC020-EN-0606 Literature Order NumberSupersedes RLC-PRC020-EN-00406 Stocking Location Inland

RTHD specifications

The Trane RTHD is a highly efficient and innovative HVAC solution designed for commercial and industrial applications. With a focus on reliability, performance, and energy efficiency, the RTHD series offers a wide range of features that set it apart from conventional heating and cooling systems.

One of the standout characteristics of the Trane RTHD is its robust construction. Built to withstand the rigors of daily use in demanding environments, the unit boasts a durable and weather-resistant cabinet. This design not only ensures longevity but also helps protect internal components from external elements.

Energy efficiency is at the forefront of the RTHD's design philosophy. The unit utilizes advanced technologies such as Variable Frequency Drive (VFD) for its compressor and fans. This allows for precise adjustment of the cooling and heating output, optimizing energy consumption based on real-time demand. As a result, the RTHD can achieve impressive Seasonal Energy Efficiency Ratios (SEER) and Heating Seasonal Performance Factors (HSPF), making it an environmentally friendly choice.

Another key feature of the RTHD is its compatibility with various control systems. The unit supports Trane's advanced control technology, enabling integration with building management systems for enhanced monitoring and operational efficiency. This capability allows facility managers to leverage data-driven insights to optimize performance and maintenance schedules.

The RTHD also incorporates innovative sound-reducing technologies, which ensure quiet operation, a significant consideration for settings where noise reduction is essential. Features such as acoustic insulation and strategically designed fan blades help minimize sound levels, making the RTHD suitable for a variety of commercial environments.

Ease of maintenance is another important aspect of the Trane RTHD. The design includes accessible components for quick servicing, minimizing downtime and overall maintenance costs. Additionally, Trane provides comprehensive support and resources to ensure that technicians can efficiently maintain and troubleshoot the system.

In summary, the Trane RTHD is a leading-edge HVAC solution that combines durability, energy efficiency, advanced control options, and quiet operation. With its range of features and technologies, it is well-equipped to meet the demands of modern commercial and industrial spaces, solidifying its reputation as a trusted choice in the HVAC market. Whether for new installations or upgrades, the RTHD delivers reliability and performance that customers can depend on for years to come.