Greenheck Fan Understanding Selection: Guide to Fan Drive Selection and Exhaust Choices

Page 13

Basics of Fan Selection

The first consideration in any fan selection is the amount of air to be moved and the resistance to this air movement. With specific performance and application criteria in mind, propeller fan selections typically require decisions based on the following criteria.

Belt Drive vs. Direct Drive

Belt drive fans offer the ability to adjust fan speed for system balancing if necessary. They also offer more flexibility in speeds and motor selections. In a cost comparison, belt drive fans are typically less costly than comparable size direct drive fans with low speed motors.

Direct drive fans are often preferred for jobs where maintenance access is difficult. Maintenance costs are generally lower with direct drive fans, since there are no belts or bearings to replace and no pulleys to adjust.

Larger Fans vs. Smaller Fans

In most applications, several fans may meet the specified airflow and pressure requirements. Just as larger fans tend to turn slower and generate less sound, they also tend to have higher initial costs but lower operating costs. Smaller fans, with their higher speeds, have more stable performance curves, lower initial costs, higher sound levels, and higher operating costs.

Low Sound vs. High Static Pressure

Fans selected for high static pressures run at higher speeds and produce higher tip speeds, resulting in higher sound levels. Conversely, in low pressure applications, fans generally run at lower speed producing lower sound levels and are recommended for sound sensitive applications.

How Accessories Affect Static Pressure

All accessory losses must be accounted for when calculating a fan’s static pressure load. In most cases dampers, guards and weatherhoods actually add very little to the total system pressure. This means that propeller fans used in conjunction with common accessories can typically be specified with low pressure capabilities (below 38 in. wg). However, in cases where airflow velocities exceed 1500 fpm through the damper or where filters are used, static pressure loss may be significant. For more specific information on pressure losses due to accessories, refer to pages 9 and 10.

Motor Service Factor

Motors for sidewall propeller fans are cooled by the airstream. With an uninterrupted flow of cooling air, motors may be operated in their service factor range (up to 20% above the motor’s nameplate horsepower) without damage due to overheating. Lesser overloads are recommended for applications using totally enclosed or explosion resistant motors.

Belt drive performance tables in this catalog show two speed selections for each propeller type (L or

H)at a given motor hp. The first selection is a 1.0 bhp service factor. The second speed selection is at 1.2 bhp service factor. Direct drive performance tables show BHP levels with service factors ranging up to 1.2 bhp. When a selection at 1.2 bhp service factor is not desirable for the application, specify the next higher motor horsepower.

Direct Drive Model Number Code

The model number system is designed to completely identify the fan. The correct code letters must be specified to designate direct drive with exhaust or supply air configuration. The remainder of the model number is determined by the size and performance selected from pages 15 through 21.

S E 2 - 24 - 6 20 - B 7

Sidewall Roof Propeller

S - Fabricated Prop

SC - Cast Prop

(Level 3 only)

E - Exhaust

S - Supply

R - Reversible

Level of Construction 1, 2, 3

Fan Size

No of Blades

Motor HP

 

4 = 14

10 = 1

30 = 3

3 = 13

15 = 112

50 = 5

5 = 12

20 = 2

75 = 712

7 = 34

 

 

Motor RPM

(50Hz)

A = 1750

F = 690

B = 1160

G = 1300

C = 860

J = 1440

D = 1550

L = 1290

E = 1050

P = 1650

Blade Pitch

13

Image 13
Contents Sidewall Propeller Fans Leading Edge Technical Support Sidewall Propeller FansDirect Drive Fan Selection Model ComparisonBelt Drive Fan Selection Propeller Types Blade DesignsMounting Options Overview Mounting Fan Directly to Wall Standard Wall MountingStandard Horizontal Mounting Option 71⁄2 Wall Collar Mounting OptionClosure Angles Wall Housing Mounting OptionMounting Arrangements for Interior Service Applications Wall Housing Mounting ArrangementsDiffusers Wall Housing Mounted Manual Operator Filtered Supply Wall Housing Mounting OptionsWeatherhood Damper GuardBackdraft Dampers Volume Control/Heavy Duty DampersExhaust Gravity or Motorized ¹ Supply Gravity ²Electrical Other Options and AccessoriesOptions Propeller Fan Rotation GuideBasics of Fan Selection Direct Drive Level Dimensional Data Models SE1/SS1Model SE1 exhaust shown Sizes Model SS1 supply shown SizesModel SE1 for exhaust Model SS1 for supply Model SE2 exhaust shown Dimensional Data Models SE2/SS2Fan Panel Damper Model SE2 for exhaust Model SS2 for supply Model SCE3 exhaust shown Dimensional Data Models SCE3/SCS3Model SCE3 for exhaust Model SCS3 for supply Direct Drive Level 3 Reversible Dimensional Data Model SCR3Model SCR3 reversible shown Model SCR3 Reversible for exhaust and supply Level 3 only Belt Drive Model Number CodeFor specific motor limitations and availability see Belt Drive Level Dimensional Data Models SBE-1/SBS-1Model SBE-1H exhaust shown Model SBE-2L exhaust shown Dimensional Data Models SBE-2/SBS-2Belt Drive Level 3 and Reversible Dimensional Data Models SBE-3/SBS-3, SBCE-3/SBCS-3 and SbcrLevel 3 Model SBE-3L exhaust shown Reversible Model Sbcr reversible shownBelt Drive SBE/SBS Using The Performance TableModel SBE for exhaust Model SBS for supply 3877 3734 36184157 4041 4641 45356593 57476970 721018044 12744 1191513814 1471216281 1414417349 18723 1595321490 1866022867 23708 2025233548 3057735664 35214 40314 39911 39104Cast Aluminum Model Sbce for exhaust Model Sbcs for supply Belt Drive SBCE/SBCS12655 1101413442 1392124128 2101025650 2657832868 29286 2994334870 31476 37564 34371Reversible Exhaust and Supply Belt Drive SbcrBelt Drive Belt Drive SpecificationsReversible Belt Drive Reversible Direct Drive Direct Drive