Greenheck Fan dimensions Model SMD-401, Ratings, Standard Construction, Size Limitations

Page 1

 

 

 

 

Model SMD-401

APPLICATION

 

 

Smoke Dampers

Model SMD-401 is a class I leakage rated smoke damper. High strength,

Extruded Airfoil Blades

streamlined extruded airfoil blades insure lowest resistance to airflow in

 

 

UL 555S Leakage Class I

HVAC systems with velocities to 3000 fpm (15.2 m/s) and 6 in. wg (1.5

 

kPa). Model SMD-401 may be installed vertically (with blades running

 

 

 

horizontal) or horizontally and is rated for airflow and leakage in either

 

Model SMD-401 meets the requirements for smoke

direction.

 

 

dampers established by:

Ratings

 

 

National Fire Protection Association

Leakage:

UL 555S leakage class I. Leakage

 

NFPA Standards 92A, 92B, 101 & 105

Velocity:

rated in both directions

 

IBC International Building Codes

Operational rated to 3000 fpm

 

New York City (MEA listing #260-91-M)

 

 

(15.2 m/s) for sizes up to

 

 

 

 

California State Fire Marshall

 

 

48 in. W x 108 in. H or 144 in. H x 36 in. H

 

 

(1219mm x 2743mm) or

 

Listing#: 3230-0981:108 (smoke)

 

 

(3658mm x 914mm) or

 

 

 

 

 

2000 fpm (10.2 m/s) for sizes

 

 

 

 

 

greater than that. Rating is for

 

“UL CLASSIFIED (see complete marking on

 

 

airflow in either direction through

 

 

 

 

product)”

 

 

damper.

 

Temperature:

250°F (121°C) with all actuators.

 

“UL CLASSIFIED to Canadian safety standards

Maximum Pressure:

6 in. (1.5 kPa)

 

 

(see complete marking on product)”

 

 

 

 

Standard Construction

 

Standard 555S (Listing #R13317)

 

 

 

Frame:

5 in. x 1 in. (127mm x 25mm)

 

 

 

 

 

galvanized steel hat channel with

 

 

 

 

 

reinforced corners. A low profile

 

 

 

 

 

head and sill are used on sizes less

 

 

 

 

 

than 17 in. (432mm) high to

 

 

 

 

 

maximize free area and

 

 

 

 

 

performance.

 

 

 

Blades:

Airfoil shape constructed of heavy

 

 

 

 

 

gauge extruded aluminum.

 

 

 

 

 

Structural reinforcement through

 

 

 

 

 

the entire length.

 

 

 

 

Seals:

Extruded silicone rubber blade

 

 

 

 

 

seals. Flexible stainless steel jamb seals.

 

 

Linkage:

Concealed in jamb.

 

 

 

 

 

 

 

Axles:

12 in. (13mm) dia. plated steel.

 

 

 

Bearings:

Bronze sleeve type

 

 

 

Size Limitations:

 

 

 

 

Minimum Size:

8 in. W x 8 in. H (203mm x 203mm)

LH

 

 

H*

Maximum Size:

 

 

Single Section:

48 in. W x 60 in.

 

 

 

 

 

(1219mm W x 1524mm H)

 

 

 

Multiple Section:

192 in. W x 72 in. H

 

(4877mm W x 1829mm H) or

 

48 in. W x 288 in. H

 

(1219mm W x 7315mm H) or

 

384 in. W x 36 in. H

 

(9754mm W x 914mm H)

Optional Features:

Galvanized steel sleeves

Stainless steel bearings

OCI (Open closed indication switches)

Electric or pneumatic actuators to accomplish smoke management and system functions.

POC retaining angles

Smoke detector

Momentary switch

Transformer

W*

RH

*W&H dimensions furnished approximately 1/4 in. (6mm) undersize. (Add sleeve thickness for overall sleeved damper dimension)

Right hand drive is shown. Left hand drive is available upon request.

Installation instructions available at www.greeenheck.com

Image 1
Contents Model SMD-401 Optional FeaturesRatings Standard ConstructionAmca Test Figures Pressure Drop Data SMD-401Damper Size 12 in. x 12 Damper Size 24 in. x 24Space Envelopes Required for Actuators and Accessories Damper Sideplate and Sleeve Dimensional DataApplication Data Specifications Transitioned Damper DimensionsDamper Sizing Information