Size Limitations
| Damper model | Maximum Single | Maximum Overall size for |
| |
|
| Section size |
| ||
| 32 in. x 32 in. | 64 in. x 32 in. |
| ||
|
| (813mm x 813mm) | (1626mm x 813mm) |
|
|
|
| 32 in. x 32 in. | 64 in. x 32 in. |
| |
|
| (813mm x 813mm) | (1626mm x 813mm) |
| |
| 32 in. x 32 in. | 64 in. x 32 in. |
| ||
|
| (813mm x 813mm) | (1626mm x 813mm) |
| |
| 32 in. x 32 in. | 64 in. x 32 in. |
|
| |
|
| (813mm x 813mm) | (1626mm x 813mm) |
| |
|
|
|
|
|
|
|
|
|
|
|
|
Manually operated dampers (IMO-310 & SSIMO-310)
Manually operated dampers utilize a spring and fusible link assembly to close the damper during elevated temperature conditions. No electrical power is required for these models.
Motor operated dampers (IMO-311 & SSIMO-311)
Motor operated dampers are supplied with an electric thermal response device which cuts power to the spring return actuator upon sensing an elevated temperatures. See below for electrical connections.
Connection and Operation of Temperature Response Devices (RRL standard, OCI option, and PRV option)
RRL - Dampers will be supplied with a
thermostat.
If RRL is ordered with a pneumatic actuator, an EP switch is required with an appropriate electric power circuit to allow the electric thermostat to control the pneumatic actuator.
OCI - The OCI (open or closed indicator) option contains a single pole, double throw switch used to indicate the damper blade position. The switch provides a positive open or closed signal when used in conjunction with remote indicator lights. Refer to Fig. 7 for wiring of the OCI option.
ELECTRICAL CAPACITY = 10 AMP @ 120 / 240 VAC
L1 |
|
| RRL Wiring | L2 | |
ORANGE | NC | BLACK | BLACK | M WHITE/RED | |
| |||||
|
| P |
|
|
|
|
| PRIMARY TEMP | ELECTRIC DAMPER | ||
|
| SENSOR |
| ACTUATOR OR PNEUMATIC | |
Fig. 5 |
|
|
| SOLENOID VALVE | |
|
|
|
|
| |
NOTE: THE SWITCH WIRES WRAPPED WITH | |||||
| A BLUE MARKER INDICATE THE |
| |||
| CLOSED POSITION OF THE DAMPER. | ||||
ELECTRICAL CAPACITY = 10AMP @ 120 / 240VAC | |||||
L1 |
|
|
|
| L2 |
|
|
| OCI Wiring |
| |
|
|
|
|
| BY OTHERS |
YELLOW S1 | YELLOW |
|
| ||
|
| NO |
|
| DAMPER |
|
|
|
| INDICATOR | |
YELLOW |
| S2 | YELLOW |
| |
|
| LIGHTS | |||
|
|
|
NO
PRV - The PRV (pneumatic relief valve) option is heat responsive |
| Fig. 6 |
| |
|
|
| ||
device used with pneumatic actuators. This can be used in place |
|
|
| |
of EP switch where a RRL is used. The PRV activates when | RATINGS | |||
temperature in excess of the temperature of the fusible link are |
|
|
|
|
detected. When the fusible link melts, air from the actuator is | Integral Switch Type: Single Pole, double throw | |||
exhausted to close the dampers. Pneumatic actuators are to be |
|
|
|
|
piped per local code. |
| Electrical Capacity: 10 Amps, 1/3 hp, 120 or 240 Vac |
1/2 Amp, 125 Vdc; 1/4 Amp 250 Vdc 5 Amps, 120 Vac “L” (lamp load) 1.0 Amps, 24 Vac
1.5 Amps, 24 Vdc
Temperature Limit: 165° F (standard primary sensor) 212° F (optional primary sensor)