Greenheck Fan OSSFD-XXX Series, OFSD-XXX Series, ODFD-XXX, OFD-XXX Series Damper Maintenance

Page 6

Damper Maintenance

Dampers do not typically require maintenance as long as they are kept dry and clean. If cleaning is necessary, use mild detergents or solvents. If lubrication is desired for components such as axle bearings, jackshaft bearings and jamb seals, do not use oil-based lubricants or any other lubricants that attract contaminants such as dust.

Dampers and their actuator(s) must be maintained, cycled, and tested a minimum in accordance with:

The latest editions of NFPA 80, 90A, 92A, 92B, 101, 105, UL864, AMCA 503-03 and local codes.

Actuator manufacturer recommendations.

Damper Troubleshooting

The following is a possible cause and correction list for common concerns with the dampers.

Symptom

Possible Cause

Corrective Action

 

Frame is 'racked' causing blades

Adjust frame such that it is square and plumb

 

to bind on jamb seals

 

 

 

 

 

Actuator linkage loose

Close damper, disconnect power, adjust and

Damper does not

 

tighten linkage

 

 

fully open and/or

Defective motor

Replace

close

 

 

Screws in damper linkage

Damper installed too far into wall. Move out

 

 

 

to line as designated on damper label

 

Contaminants on damper

Clean with a non-oil based solvent (see

 

 

Damper Maintenance)

RRL or TOR sensor

Heat

Push reset button located on backside of

tripped

 

RRL or TOR

 

 

 

Damper does not

No power supplied to the actuator

Add power supply

operate

 

 

 

 

 

Copyright © 2008 Greenheck Fan Corporation

461337 OFSD ODFD Rev 9 January 2008

6

Image 6
Contents Installation, Operation, and Maintenance Instructions Part NumberOFD-XXX, and OSSFD-XXX Series Table of Contents Clearance Requirements Damper is Installed Outside of Wall PlaneOFSD-XXX Duct to Sleeve ConnectionsSecuring the DAMPER/SLEEVE Assembly to Wall Openings Actuator ConnectionsBlanket duct continuation See Fig Round and Oval Duct Breakaway Connections Breakaway ConnectionsTraditional Breakaway Style Transverse Joints Manufactured Flanged System Breakaway ConnectionsDamper Maintenance