Carrier HS070-160 manual Keyboard Display Comments Entry Response

Page 15

 

KEYBOARD

 

DISPLAY

COMMENTS

 

ENTRY

I RESPONSE

 

 

 

3

TEST

 

 

 

 

y$.

q

u

 

COMP

Factory field test of compressors

 

 

 

 

 

subfunction of test function

 

ENTR

 

CAM

OFF

Circuit A, compressor 1 test

 

q

 

CA1 ON

Pressing ENTR starts the test; when the

 

 

 

 

 

 

compressor should be running the

 

 

+

I

 

 

display shows CA1 on

 

 

CAM

OFF

If the test is allowed to time out, the

 

q

 

 

 

display will show CA1 o f f

 

 

C A 2

O F F

Pressing the down arrow key advances

 

 

 

 

 

 

the system to circuit A, compressor 2 test

 

 

 

 

END TEST

If no other test is desired, exit quick test

 

 

 

 

 

 

 

Refer to Fig. 5,6 and 7 for specific control wiring. Each module in a panel is numbered ( I, 2,3,4...). Each terminal strip is labeled (52, 53, J4...). The terminal strip on the machine schematic combines the module and strip numbers. For example, 2JJ is terminal strip 53 o n module 2. The module numbers can be found on the com- ponent arrangement label.

T h e m (;;;;I subfunction checks the thermistor and

switch inputs. The thermistor tests display the tempera- ture that the thermistor is reading. If the display and the actual temperature do not match, the thermistor and the input channel can each be checked.

To check the thermistor, disconnect its leads from the PSI0 terminal (the entire connector can be pulled from the PSI0 by pulling the connector to the left). Read the resistance of the thermistor, then find the corresponding temperature in Table 8.

This temperature should match the actual temperature to which the thermistor is exposed.

The thermistor can be checked while connected to the

processor by measuring the voltage across its terminals and finding the corresponding temperature in Table 8. This method can only be used if it is certain that the processor circuits are putting out the correct voltage. If there is any doubt, the thermistor should be checked by the resistance method.

The input channel can be tested by removing the

thermistor from the terminals and attaching a fixed resistor with a value between 40,000 ohms and 400 ohms. Refer to Table 8 and find the temperature that cor- responds to that resistance; this temperature should appear in the Quick Test display.

Loss of charge and oil pressure switch tests show LOW if the switch is open and NRM or SAFE if the switch is closed. The input channel can be tested by disconnecting the switch and using a jumper to simulate a closed or open circuit. (See Fig. 5.)

Note that the switch is read by the processor period- ically, not continuously. When the switch position is changed, it may take a few seconds before the display changes.

T h e [q Fi subfunction will energize the control

outputs except for the compressor control outputs. (See Fig. 6.)

The liquid line solenoid and unloader solenoid tests

will energize the output when ENTR is pressed. It will cl

remain energized until either the J key is pressed or 0

10 minutes have elapsed. When the processor energizes the output reiay it will display the word ON on the right side of the display.

The EXV open and close tests drive the EXV fully open or fully closed. See The EXV Checkout Procedure for

more information. The display will read either zero steps open or 760 steps open.

T h e 14 I;;;;] subfunction energizes the compressor

control relays for 10 seconds and displays the compressor status feedback.

The liquid line solenoid in the same circuit will ener- gize for 10 seconds and the EXV will open 180 steps, then close.

When control power reaches the compressor control relay it also reaches the feedback terminal on terminal strip 233 (see Fig. 7). When this occurs the display will

switch from OFF to UN. If the display changes but the compressor does not start, check the control relay, con-

tactor, compressor circuit breaker, interconnecting wiring, and the compressor motor.

If the display does not change, check the discharge gas thermostat, high-pressure switch, condenser fan overload (on 30HS, if used), continuity across the DSIO terminals and interconnecting wiring.

To protect the compressors from repeated cycling, a delay of one minute is required before the same com- pressor is retested.

The 4 TEST subfunctions take the unit out of the Quick Testqmodea. Press 14 H and the display will

show EKD TEST; press ENS and the display blinks and

cl

then shows END TEST again.

15

Image 15
Contents Controls Troubleshooting Guide Up Arrow Rtjturnipg to Keyboard and Display Module Control Sequence Controls Operation Keyboard Entry Display Description S E T El4 Keyboard Directory cant Operating Modes Alarms III Programming Functions Troubleshooting Compwssor is not running T21 Keyboard Display Comments Entry Response Compressor 24-V Control Circuit Wiring Simplified Thermistsr Temperature vs Resistance and Voltage English Thermistor Temperature vs Resistance and Voltage Sk Electronic Expansion Valves Thermistor Locations Electronic Expansion Valve Thermistor Compressor and Cooler Modules MoN Keyboard/Display Module I-ISIO Symptoms Page 1 1

HS070-160 specifications

The Carrier HS070-160 is a high-efficiency air conditioning unit renowned for its robust performance and advanced technological features, making it an optimal choice for both commercial and industrial applications. This model is a part of Carrier's commitment to providing reliable and energy-efficient climate control solutions tailored to meet diverse cooling needs.

One of the standout features of the HS070-160 is its impressive cooling capacity, which ranges from 70 to 160 tons. This range makes it suitable for various environments, from large office buildings to manufacturing facilities. The unit is designed with versatility in mind, offering the option for both air-cooled and water-cooled configurations, thereby allowing users to choose the most suitable setup for their specific installation needs.

The HS070-160 incorporates a state-of-the-art variable speed drive technology, which enables the compressor to adjust its speed according to the cooling demand. This not only results in enhanced energy efficiency but also improves overall comfort by providing more consistent temperature control. Additionally, the unit features high-efficiency scroll compressors that further improve its performance while minimizing energy consumption.

In terms of construction and durability, the HS070-160 is built to withstand harsh environmental conditions. The unit is equipped with corrosion-resistant coatings and sturdy components, ensuring longevity and reliable operation across a broad range of settings. The design also promotes ease of maintenance, with accessible service points that simplify routine checks and repairs.

Another noteworthy characteristic of the Carrier HS070-160 is its advanced control systems. The unit can be integrated with smart building management systems, allowing for precise monitoring and control of HVAC operations. This integration helps facility managers optimize energy usage and reduce operational costs while maintaining comfortable indoor climates.

Furthermore, the HS070-160 adheres to stringent environmental standards, making it an eco-friendly choice. It is compatible with low-GWP refrigerants, aligning with global efforts to reduce greenhouse gas emissions.

In conclusion, the Carrier HS070-160 combines efficiency, durability, and advanced technology, making it a top contender for businesses looking to invest in dependable air conditioning solutions. Its comprehensive features and characteristics not only enhance performance but also contribute to significant energy savings and environmental sustainability.