Carrier 060, 30HL050 Check Refrigerant Charge, Typical Deadband Requirements, Deadband Setting

Page 26

Table 5 Ð Typical Deadband Requirements

UNIT

 

COOLER DESIGN RANGE, F (C)

CAPACITY

 

 

 

 

 

 

STEPS

5.0 (2.8)

10.0 (5.6)

15.0 (8.3)

2

1.3

(0.7)

2.5

(1.4)

3.8

(2.1)

3

0.8

(0.4)

1.7

(0.9)

2.5

(1.4)

4

0.6

(0.3)

1.3

(0.7)

1.9

(1.1)

 

 

 

 

 

 

 

Table 6 Ð Deadband Setting

MIN. REQUIRED DEADBAND

DEADBAND SETTING (F)

F

C

 

0.5 to 1.5

0.28 to 0.83

1.0

2.0

1.11

2.0

2.5

1.39

2.5

3.0

1.67

2.8

3.5

1.94

3.0

4.0

2.22

3.7

4.5

2.50

4.0

 

 

 

10.Check compressor oil charge (should be visible in oil sight glass). Refer to Check Oil Charge section on page 27.

11.Be sure the compressor crankcase heater is warm (heater should be on for 24 hours before starting the compres- sor). The crankcase heater must be ®rmly locked into the compressor crankcase.

12.Be sure the compressor is ¯oating freely on the com- pressor springs (see Step 4 Ð Check Compressor Mount- ing and Connections section on page 3).

13.For 30HL and HWA units with remote condenser, check the condenser fans for correct rotation. See instructions shipped with the condenser.

14.Be sure the unit is fully charged with refrigerant (see Check Refrigerant Charge section below).

15.If unit is a brine unit, check to ensure proper brine con- centration is used to prevent freezing.

Check Refrigerant Charge

When adding or removing refrigerant charge, circulate water through condenser and cooler at all times to pre- vent freezing. Freezing damage is considered abuse and is not covered by Carrier warranty.

The 30HK, HWB, HWC, and HWS units are shipped with a full refrigerant charge (see Tables 1A-2B). However, if it is necessary to add refrigerant, operate the unit for some time at full capacity and then add charge until the sight glass is clear of bubbles. For maximum liquid subcooling, liquid level should be up to condenser end (30HK, HWC, HWS units only). This usually requires additional refrigerant charge be- yond the amount to clear sight glass.

The 30HL and HWA units (condenserless) are shipped with a refrigerant holding charge only. After chiller assembly is completed in the ®eld, system must be fully charged. While the unit is running at full capacity, add refrigerant until the sight glass is clear. R-22 is the normal refrigerant.

Do not open the liquid valve or the compressor discharge valve until there is a charge in remainder of system. A posi- tive pressure indicates a charge in system. With the unit op- erating at full load, check liquid line sight glass to be sure the unit is fully charged (bubbles in the sight glass indicate the unit is not fully charged).

If there is no refrigerant vapor pressure in the system, the entire system must be leak tested. After repairing leaks, evacu- ate the system before recharging. Follow approved evacu- ation procedures when removing refrigeration. Release re- maining pressure to an approved evacuated cylinder.

The liquid charging method is recommended for com- plete charging or when additional charge is required.

Be careful not to overcharge the system. Overcharging results in higher discharge pressure with higher cooling water consumption, possible compressor damage, and higher power consumption.

LIQUID CHARGING METHOD Ð Add charge to the unit through the liquid line service valve. Never charge liquid into the low-pressure side of the system.

1.Frontseat (close) condenser liquid line shutoff valve.

2.Connect a refrigerant cylinder loosely to the charging valve connection of the liquid line shutoff valve. Purge the charg- ing hose and tighten the connections.

3.Open the charging valve.

4.If the system has been dehydrated and is under vacuum, break the vacuum with refrigerant gas. For R-22, build up system pressure to 58 psig and 32 F (400 kPa and 0° C). Invert the refrigerant cylinder so that the liquid refrigerant will be charged.

5.a. For complete charge of 30HK, HWB, HWC, and HWS units, follow charging by weight procedure. When charge is nearly full, complete the process by observing the sight glass for clear liquid ¯ow. The use of sight glass charging is valid only when unit is operating at full capacity (no unloaders energized).

b.For complete charge of 30HL and HWA units or where refrigerant cylinder cannot be weighed, follow charg- ing by sight glass procedure. The use of sight glass charging is valid only when unit is operating at full capacity (no unloaders energized).

6.a. The 30HL and HWA condenserless units are shipped with a holding charge only. After installation with the ®eld-supplied system high side, the complete system should be charged until the sight glass is clear (with the unit running at full capacity). To achieve maxi- mum system capacity, add additional charge equal to the difference between the condenser optimal charge and the condenser minimum charge, which can be ob- tained from the charge data provided in the condenser installation instructions.

b.To ensure maximum performance of 30HWB units, raise the compressor saturated discharge temperature (SDT) to approximately 105 F (40.6 C) by throttling the condenser water intake. Add charge until there is approximately 15 to 17° F (8.3 to 9.4° C) of system subcooling (SDT minus actual temperature entering the thermostatic expansion valve).

c.To ensure maximum performance of 30HK, HWC, and HWS units, raise the compressor saturated discharge temperature (SDT) to approximately 103 F (39.4 C) by throttling the condenser water intake. Add charge until there is approximately 8 to 10° F (4.4 to 5.6° C) for 30HK units or 12 to 14° F (6.7 to 7.8° C) for 30HWC, HWS units of system subcooling (SDT minus actual temperature entering the thermostatic expansion valve).

26

Image 26
Contents Installation, Start-Up Service Instructions ContentsSafety Considerations GeneralPlace the Unit InstallationRig and Place Unit 30HW UnitsUnit TOP ViewLeft Side View SAE30HL050,060 Condenserless TOP View Front View Right Side ViewRear View Left Side View 30HWB018-040 Fluid Cooled 30HWBLeft Side View Front View 30HWC,SLocation of Mounting Holes Weight Distribution AT Each Mounting HOLE, 60 HZ UnitsWeight Distribution AT Each Mounting HOLE, 50 HZ Units 30HWA,B 30HWC,SCompressor HWBHWC,S CoolerRefrigerant Ð kg Condenser Connections Ð Physical Data 30HL, HWA Condenserless Units Ð EnglishÐ Physical Data 30HL, HWA Condenserless Units Ð SI Factory-Installed Unit Wheels Typical Piping with Fluid-Cooled 30HWB Unit Shown Page Installed Coupling Fastening Grooved Pipe Ends Cooler DescriptionCooler Pressure Drop Ð 30HW Units Minimum Cooler and Condenser Flow Rates Minimum Loop VolumeUnit Size Cooler Condenser Minimum Cooler Loop VOLUME² Cooler Pressure Drop Ð 30HK, HL UnitsCondenser Pressure Drop Ð Page ICF Ð Electrical Data Ð 30HK, HWB, HWC, HWS Fluid-Cooled UnitsUnit Size LRA MTAÐ Electrical Data Ð 30HL and HWA Condenserless Units DLS Field Accessory WiringCWP GCSGND COMEquip TORSEC PRIHGS HPSElectric Shock Hazard PRE-START-UPInitial Check NeutTypical Deadband Requirements Deadband SettingCheck Refrigerant Charge Check Refrigerant Feed Components START-UP and OperationOperating Limitations To ADD OILCheck Unit Safeties Pressure Relief Valve SettingsCompressor and Unit Protective Devices Crankcase HeaterFactory Settings, High-Pressure Switch Fixed Factory Settings, Low-Pressure Switch FixedFREEZE-UP Protection Unit OperationCapacity Control and Operating Sequence Ð Transfer Switch Compressor Unit Control No Position Steps Capacity Control Steps Ð 30HK, HL Standard UnitsUnit Capacity Control Operating ServiceCapacity Control Steps Ð 30HW Standard Units Steps CylindersThermistor REPLACEMENT, 30HK, HL Units ThermistorÐ Sensor Temperature F vs Resistance Temperature Resistance OhmsÐ Sensor Temperature C vs Resistance Plugs and Tubes Servicing Cooler 30HK,HL onlyTightening Cooler Head Bolts Components for Part Number PluggingHead Bolt Tightening Sequence TroubleshootingChilled Fluid PROOF-OF-FLOW Switches Open Troubleshooting Symptoms Cause RemedyCompressor Service Training Call for Free CatalogPreliminary Equipment Check YES or no START-UP Checklist for Chiller SystemsRemove and use for job le Preliminary Information LOCATE, REPAIR, and Report ANY R-22 Leaks Voltage ImbalanceFluid Leaving Cooler Unit Start-UpFluid Entering Cooler Units Rated MIN. Pressure Drop =Book Catalog No Form 30H-10SI Pg CL-4 11-98

30HK040-060, 060, 30HL050, 30HW018-040 specifications

The Carrier 30HW018-040, 30HL050, 060, and 30HK040-060 series represents a range of advanced rooftop units designed to meet the diverse heating and cooling needs of commercial buildings. Renowned for their efficiency and performance, these units incorporate cutting-edge technologies to improve operational effectiveness and reduce energy consumption.

One of the standout features of the Carrier 30HW series is its high-efficiency scroll compressors, which are engineered to provide exceptional cooling capacity while minimizing energy usage. These compressors operate quietly and ensure smooth performance across varying loads. Additionally, the units utilize advanced microprocessor controls that enhance system efficiency by enabling precise temperature regulation and optimizing energy consumption based on real-time weather conditions.

Another important aspect of the 30HL series is its ability to provide reliable heating and cooling capabilities even in extreme weather conditions. With robust heat exchangers and a range of variable-speed fans, these units can efficiently circulate air while maintaining optimal indoor comfort levels. Variable-speed technology not only enhances comfort but also improves energy savings, as the system can adjust its output based on occupancy and external temperature fluctuations.

The 30HK series, specifically designed for high-performance applications, features enhanced filtration systems which improve indoor air quality. These systems are capable of accommodating various filter types, ensuring that airborne contaminants are effectively captured. This makes the 30HK a suitable choice for environments where air quality is a priority, such as schools, hospitals, and commercial offices.

Moreover, all units in the 30HW, 30HL, and 30HK series are designed with ease of maintenance in mind. Removable panels and easy access points allow for quick servicing and reduces downtime. The compact design also ensures that installation is straightforward, making them a preferred choice for many contractors.

In summary, Carrier's 30HW018-040, 30HL050, 060, and 30HK040-060 series are integral solutions in the HVAC market, combining energy efficiency, advanced controls, and superior air quality features. These rooftop units are tailored for commercial applications, providing reliable heating and cooling solutions while prioritizing comfort and sustainability. Through continuous innovation, Carrier remains at the forefront of HVAC technology, ensuring that their products meet the evolving demands of the industry.