Bryant ERVBBLHA manual Control Features, Automatic Defrost Cycle Features, Below, Defrost Exchange

Page 5

CONTROL FEATURES

CONTROL

FAN SPEED

DEHUMIDISTAT

CONTINUOUS

INTERMITTENT

DESCRIPTION

CONTROL

CONTROL

MODE

MODE

 

 

 

 

 

OneTouch

Yes

No

Yes

Yes

Basic

Yes

No

Yes

No

 

 

 

 

 

Standard

Yes

Yes

Yes

Yes

 

 

 

 

 

Basic Control:

Allows the user to manually set fan speed to low or high as required to maximize comfort.

Standard Control:

Offers automatic dehumidistat control and the option to select continuous or intermittent fan operation. Setting the wall control to low will activate the continuous mode.

OneTouch Control:

Allows control of ventilator with the touch of a button. This control will operate as a main wall control. The OneTouch will operate the unit in Intermittent Mode (20 minutes per hour), continuous low speed, continuous high speed, and off.

AUTOMATIC DEFROST CYCLE FEATURES

All models offer a non-electric defrost cycle feature which prevents frost and ice buildup within the heat recovery core. When the outside air temperature falls below 23_F (-5_C) it is electronically sensed and the dampers close the outside air ports. This allows warm indoor air to recirculate within the heat recovery core. The frequency of this cycle increases as the outside air temperature decreases.

 

25_F TO 55_F

 

---4_F TO

17_F

 

BELOW

---18_F

MODEL

(---5_C TO ---

15_C)

(---15.6_C TO

---27.3_C)

---( 27.8_C)

 

 

 

 

 

 

 

 

 

 

 

DEFROST*

 

EXCHANGE{

DEFROST*

 

EXCHANGE{

DEFROST*

EXCHANGE{

 

 

 

 

 

 

 

 

 

 

 

ERVBBLHA

6 Minutes

 

60

Minutes

6 Minutes

 

32

Minutes

6 Minutes

20 Minutes

 

 

 

 

 

 

 

 

 

 

 

HRVBBLHA

6 Minutes

 

60

Minutes

6 Minutes

 

32

Minutes

6 Minutes

20 Minutes

 

 

 

 

 

 

 

 

 

 

 

*All defrost times are in the standard mode (as shipped)

{Time between defrost when within specified temperature range

ERV / HRV

5

Image 5
Contents Product Data Standard FeaturesModel Number Nomenclature Climate Map for Energy and Heat Recovery VentilatorsPhysical Data DimensionsElectrical Data Model ERVBBLHA1150 ERVBBLHA1200 HRVBBLHA1150 HRVBBLHA1250Model Temp AIR Flow Consumed Recovery Sensible NET Power Sensible ApparentPerformance Data Efficiency Effective Moisture CFM Ness TransferAutomatic Defrost Cycle Features Control FeaturesBelow Defrost ExchangeFloor Bedrooms Heating and Cooling Load Charts40% Ventilator installed with forced air system KIT Number Description Where Used Accessories Ventilator Accessory Number NomenclatureCatalog No. PDSERVHRVLHA---01