Carrier 62E specifications Make Electrical Connections, A62-380

Page 17

EYE HOOK (HIDDEN)

EYE HOOK

a62-380

EYE HOOKS

FORK POCKETS

Fig. 13 — Rigging and Handling

Step 7 — Make Electrical Connections

WARNING

Prior to performing service or maintenance operations on the ERV unit, turn off and disconnect all power switches to the unit. Be aware that there may be more than one discon- nect switch. Electrical shock could cause serious personal injury or death.

IMPORTANT: Only trained, qualified installers and ser- vice technicians should install, wire, start-up and service equipment.

POWER SUPPLY — The electrical characteristics of the available power supply must agree with the unit nameplate rating. Supply voltage must be within the limits shown. See Ta- bles 3-5 for electrical and configuration data.

ELECTRICAL CONNECTIONS — The ERV unit must have its own electrical disconnect box. If the disconnect option has not been ordered from the factory, it must be field supplied and installed per local codes. See Tables 3-5.

If the ERV unit has an electric pre-heater factory installed, it will be wired through the ERV unit disconnect.

Low Voltage Wiring — Wire low voltage per Fig. 14. The field connection terminal strip is located behind the panel that is adjacent to the control box. The correct panel is marked with a green label stating “Attention: For field control of ERV, re- move this panel to gain access to ERV field control terminal strip.” The wires connecting to the field terminal strip can be routed through the nearest 3/4-in. hole and through conduit to the RTU, or they can be routed down the sidewall of the cabi- net using the wire pull provided and routed through the combi- nation curb to the RTU.

CAUTION

When routing wires in the ERV always keep them away from moving parts and sharp metal edges. Follow all local and state codes when routing the ERV control wires.

If the ERV unit is mated to a RTU, terminals C and G on the field control terminal strip of the ERV unit are connected to the corresponding terminals on the RTU cabinet. Verify the jumper is removed from the “ERV R” and “G” terminals; not doing so may damage RTU control equipment.

When the ERV is to be run as a stand-alone configuration, verify that a jumper is shorting the “ERV R” and “G” terminals

on the ERV field control terminal strip. This will enable the ERV to turn on and run.

If the HVAC unit has an integrated economizer or power ex- haust, it is sometimes necessary to provide an interface be- tween the HVAC unit and the ERV controls to ensure proper operation of the ERV’s supply/exhaust fan and energy recovery wheel motors. The 62E has discrete inputs for this purpose and damper end switches or relays may be used to coordinate the economizer and power exhaust operation with the ERV.

When an ERV is mated to an electro-mechanical rooftop unit with an economizer and a power exhaust, terminals C and G on the ERV field control terminal strip are still connected to the corresponding terminals on the rooftop unit cabinet (jumper across R and G needs to be removed). However, in addition, field supplied and installed end switches are required to coordi- nate operation with the unit. For unit economizer operation, it is necessary to install an Normally Open end switch (field pro- vided) on the economizer actuator and connect to terminals 5 and 6 (ERV Shutdown) on the ERV terminal strip. This will cause the ERV to shut down during unit economizer operation. For power exhaust, based on building pressure control, no ad- ditional ERV wiring is required, however if the ERV is to pro- vide power exhaust functionality then a field-installed Normal- ly Closed end switch is required to be installed between termi- nals 7 and 8 on the ERV terminal strip.

High Voltage Wiring — Connect high voltage wiring to the disconnect, see Fig. 14. Route the power wires in water tight conduit from the disconnect switch box to the ERV distribution block. To gain access to high voltage block, remove panel marked with label stating, “High voltage terminal block locat- ed behind this panel.”

Table 3 — ERV Wheel Motor and Control

Transformer Electrical Data

 

UNIT

ERV WHEEL MOTOR

CONTROL

UNIT

TRANSFORMER

 

 

 

 

 

V-Ph

V-Ph

 

W

FLA

V

FLA

 

 

 

 

115-1

115-1

 

80.5

0.70

75

0.65

 

230-1

230-1

 

69.0

0.30

75

0.33

62EB,E7

230-3

230-1

 

69.0

0.30

75

0.33

400-3

230-1

 

69.0

0.15

75

0.16

 

 

 

460-3

230-1

 

69.0

0.15

75

0.16

 

575-3

230-1

 

69.0

0.12

75

0.13

 

230-1

230-1

 

69.0

0.30

75

0.33

 

230-3

230-1

 

69.0

0.30

75

0.33

62EC,E2

400-3

230-1

 

69.0

0.15

75

0.16

 

460-3

230-1

 

69.0

0.15

75

0.16

 

575-3

230-1

 

69.0

0.12

75

0.13

 

230-3

230-1

 

69.0

0.30

75

0.33

62ED,E3

400-3

230-1

 

69.0

0.15

75

0.16

460-3

230-1

 

69.0

0.15

75

0.16

 

 

 

575-3

230-1

 

69.0

0.12

75

0.13

 

230-3

230-3

 

138.3

1.04

75

0.33

62EE,E4

400-3

460-3

 

138.3

0.52

75

0.16

460-3

460-3

 

138.3

0.52

75

0.16

 

 

 

575-3

575-3

 

99.7

0.30

75

0.13

 

230-3

230-3

 

99.7

0.75

75

0.33

62EH,E5

400-3

460-3

 

101.0

0.38

75

0.16

460-3

460-3

 

101.0

0.38

75

0.16

 

 

 

575-3

575-3

 

99.7

0.30

75

0.13

 

230-3

230-3

 

332.4

2.50

75

0.33

62EK,EL,EM,

400-3

460-3

 

319.1

1.20

75

0.16

EN,EP,E6

460-3

460-3

 

319.1

1.20

75

0.16

 

575-3

575-3

 

315.8

0.95

75

0.13

 

230-3

230-3

 

452.0

3.40

75

0.33

62ER,ES,

400-3

460-3

 

452.0

1.70

75

0.16

ET,EU

460-3

460-3

 

452.0

1.70

75

0.16

 

575-3

575-3

 

465.3

1.40

75

0.13

 

LEGEND

 

 

 

 

 

 

FLA — Full Load Amps

W

Watts

 

 

 

17

Image 17
Contents General ContentsSafety Considerations Physical Data SI Unit 62E Physical Data English Nominal Capacity cfm Supply/Exhaust Fan Options Physical Data SI InstallationSupply/Exhaust Fan Options Physical Data English FAN Option CodeRTU ERVType A62-33062E Unit A62-331 62EL-62EU Unit Cabinet DimensionsA62-246ef A62-247efA62-376.eps A62-377 Dimension Unit TypeA62-443 A62-37862E Unit Type 62E2-62E7 Unit Cabinet DimensionsInstall Standard Roof Curb A62-442 62E2-62E7 Unit Roof Curb DimensionsA62-379 62EB-62EU Unit Horizontal Discharge Box DimensionsA62-380 Make Electrical ConnectionsUnit FAN Motor Option Chassis FLA Supply and Exhaust Fans Electrical DataHeater Unit and Heater 62E Chassis FLA Electric Heat Electrical Data62.83 Typical Wiring Schematic A62-383.eps Energy Recovery WheelSTART-UP Airflow vs. Pressure Drop Across ERV Wheel Airflow VS. Pressure Drop Across ERV Wheel Unit EpsFig Outside Air Cfm ScreenA62-388.epsFig Modulating Cfm Eps Exhaust Air Offset ScreenFalse True Rmcorp Wiring Specifications Recommended Vendors and Part NumbersAWG CL2PUPC Open Controller NEC MS/TP Wiring RecommendationsSpecification Recommmendation Baud Selection Table SW3 Protocol Switch Settings For MS/TPUPC Communication Protocol Settings DIP Switches Bacnet Point Name Read Object ID Write Object Name Network Points ListService A62-278ef Installing Wheel SegmentsA62-279ef A62-280ef Belt ReplacementA62-281ef A62-282efPulley Location A62-284efA62-285ef MaintenanceReplacing a Blower 62EB and 62E7 Units A62-286ef Diameter Seal AdjustmentSymptom Possible Causes Action to Check Possible Remedy TroubleshootingERV Troubleshooting Page Coupled to RTU or stand-alone Specify RTU Application

62E specifications

The Carrier 62E is a highly regarded air conditioning unit known for its efficiency, reliability, and advanced technology features. Designed to cater to both residential and light commercial applications, this model is recognized for its ability to provide optimal cooling performance even in challenging climates.

One of the standout features of the Carrier 62E is its energy efficiency. The unit boasts a high Seasonal Energy Efficiency Ratio (SEER) rating, which ensures significant energy savings over time. This efficiency not only translates to lower energy bills for users but also contributes positively to environmental sustainability. The Carrier 62E is designed with eco-friendly refrigerants that minimize its carbon footprint while maintaining high performance levels.

In terms of technology, the Carrier 62E comes equipped with innovative smart controls. The unit can be integrated with smart home systems, allowing users to control their cooling preferences through their smartphones or other connected devices. This feature enhances convenience, enabling homeowners to adjust temperatures and monitor their system remotely, ensuring maximum comfort regardless of their location.

The 62E is engineered with a durable and robust build, ensuring long-lasting reliability. The components are crafted to withstand harsh weather conditions, making it a solid investment for users in varied climates. Additionally, the unit operates quietly, thanks to its advanced sound-dampening technologies, ensuring that indoor environments remain peaceful and undisturbed.

Installation of the Carrier 62E is straightforward, thanks to its versatile design and flexibility. The system can be configured for various ductwork arrangements, adapting seamlessly to different home layouts and existing infrastructure.

Another notable characteristic of the Carrier 62E is its advanced filtration system. The unit comes with a high-efficiency filter that captures airborne particles, allergens, and pollutants, promoting cleaner and healthier indoor air quality. This is an essential feature for households with allergy sufferers, as it helps create a more comfortable living space.

Overall, the Carrier 62E stands out as a leader in residential and light commercial air conditioning solutions. With its energy efficiency, state-of-the-art technology, durable design, and air quality improvements, it meets the diverse needs of modern users while providing remarkable comfort throughout the year. As climate considerations become increasingly important, the Carrier 62E remains a compelling choice for those seeking to enhance their home's comfort while being mindful of energy consumption and environmental impact.