Bloomfield WVAE-30F operation manual Burn Hazard HOT OIL Spill

Page 11

M381 301603 OpM (Supplemental) NFPA Hood

 

IMPORTANT!

 

VACUUM FITTING

280ºF

DO NOT INSTALL

DISCHARGE NOZZLE

FUSIBLE LINK

HERE!

 

DISCHARGE

NOZZLES

INSIDE OF HOOD

LOOKING UP

INSTALL ON LEFT OR

INSTALL ON RIGHT

SIDE OF HOOD

SIDE OF HOOD

BACK, HORIZ.,

BACK, HORIZ.,

LEFT SIDE,

RIGHT SIDE

INSTALL (8-1/4”)

INSTALL (5-3/4”)

CENTER,

 

VERT. 3”

 

SIDE, VERT. (6”)

SIDE, HORIZ. (13-1/2”)

MANUAL PULL

STATION PIPING

FRYPOT

FUSIBLE LINK

NOTE

CABLE

ROUTED

UNDER

GUIDE

CRIMP

FERRULE

CLIP

450ºF

FUSIBLE LINK

HEATSINK

DANGER

BURN HAZARD

HOT OIL SPILL

Any additional remote pull station must not be installed on the front or sides of the fryer forward of the ventilator side panels.

Discharge of the fire extinguishing system into hot oil will cause hot foam to spill over from the frypot.

Serious burns and other injuries can result from contact with hot oil and from slipping in spilled oil.

Exclusive Anti-Fire System In the unlikely event that both the temperature control thermostat and hi-limit detector fail, and the oil temperature climbs above the safety limit, the fire suppression system will discharge, cooling the oil below the oil’s (approximately) 540ºF auto-ignition temperature, and preventing a fire from occurring.

9

Image 11
Contents Fryer Model WVAE-30F WVPE-30F WVAE-55F WVAE-55FS M381 301603 OpM Supplemental Nfpa Hood Introduction Items beginning with Description Function M381 301603 OpM Supplemental Nfpa Hood M381 301603 OpM Supplemental Nfpa Hood M381 301603 OpM Supplemental Nfpa Hood Shock Hazard Link Inside Hood Behind Filters Burn Hazard HOT OIL Spill FAN Ventilator Warning Light Panel HOT Surface Frequency Monthly M381 301603 OpM Supplemental Nfpa Hood Wells BLOOMFIELD, LLC Page Page Troubleshooting Suggestions Wells Bloomfield, LLC Genuin e Parts