Thomas & Betts FE, BE Clearances and Combustion Air contd, Suspending the Heater, Suspension

Page 6

6.Clearances and Combustion Air (cont'd)

Model

 

 

Required Clearances (inches and mm)

Size

 

Top

Flue

Sides

Bottom

Rear

 

 

 

Collector

 

 

 

25-400

6"(152)

6"(152)

18"(457)

12"(305) *

24" (610)**

 

 

 

 

 

 

 

*When supplied with optional downturn nozzle, bottom clearance is 42"(1067mm). For service purposes, on standard units, bottom clear- ance exceeding minimum (12" or 305mm) is not required but may be desirable.

**For servicing purposes only, rear must remain full open.

All fuel-burning equipment must be supplied with the air that enters into the combustion process and is then vented to the outdoors. Suffi- cient air must enter the equipment location to replace that exhausted through the heater vent system. In the past, the infiltration of outside air assumed in heat loss calculations (one air change per hour) was assumed to be sufficient. However, current construction methods uti- lizing more insulation, vapor barriers, tighter fitting and gasketed doors and windows or weather-stripping, and mechanical exhaust fans may now require the introduction of outside air through wall openings or ducts.

The requirements for combustion and ventilation air depend upon whether the unit is located in a confined or unconfined space. An "un- confined space" is defined as a space whose volume is not less than 50 cubic feet per 1000 BTUH of the installed appliance. Under all condi- tions, enough air must be provided to ensure there will not be a nega- tive pressure condition within the equipment room or space. For spe- cific requirements for confined space installation, see Paragraph 7.

WARNING: These power-vented unit heaters are designed to take combustion air from the space in which the unit is installed and are not designed for connection to outside combustion air intake ducts. Connecting outside air ducts voids the warranty and could cause hazardous operation. See Hazard Levels, Page 2.

7.Combustion Air Requirements for a Heater Located in a

Confined Space

Do not install a unit in a confined space without providing wall open- ings leading to and from the space. Provide openings near the floor and ceiling for ventilation and air for combustion as shown in Figure 1, depending on the combustion air source as noted in Items 1, 2, and 3 below the illustration.

Figure 1 - Confined Space: A space whose volume is less than 50 cubic feet per 1000 BTUH of the installed appliance input rating

Add total BTUH of all appliances in the confined space and divide by figures below for square inch free area size of each (top and bottom) opening.

1.Air from inside the building -- openings 1 square inch free area per 1000 BTUH. Never less than 100 square inches free area for each open- ing. See (1) in Figure 1.

2.Air from outside through duct -- openings 1 square inch free area per 2000 BTUH. See (2) in Figure 1.

3.Air direct from outside -- openings 1 square inch free area per 4000 BTUH. See (3) in Figure 1.

NOTE: For further details on supplying combustion air to a confined space, see the National Fuel Gas Code ANSI Z223.1a (latest edition ).

8. Suspending the Heater

Before suspending the heater, check the supporting structure to be used to verify that it has sufficient load-carrying capacity to support the weight of the unit.

Net Weight (lbs and kg)

Model

 

 

 

 

 

Size

 

 

 

 

 

Type

 

 

25

50

75

100

125

165

200

250

300

400

Fan

 

lbs

76

83

92

101

132

154

175

209

226

281

 

 

kg

34

38

42

46

60

70

79

95

103

127

Blower

 

lbs

97

104

118

130

180

206

240

278

301

395

 

 

kg

44

47

54

59

82

93

109

126

137

179

NOTE: If the installation includes an optional stepdown transformer kit (Option CF or CG), the stepdown transformer bracket is part of the heater suspension and must be installed prior to hanging the heater. Follow the instructions on the installation sheet included with the op- tion kit.

A fan-type unit heater is equipped with standard two-point suspen- sion. A 3/8-16 threaded hanger bracket assembly is located on each side of the heater. If a fan-type unit has been ordered with optional, factory-installed, four-point suspension (Option BJ6), it will have two threaded hanger brackets on each side.

A blower-type heater is equipped with standard four-point suspen- sion. Two 3/8-16 threaded hanger bracket assemblies are located on each side of the unit. Each hanger bracket assembly is designed for threaded rod attachment.

For both "standard" and "optional" suspension point dimensions, see Dimension Tables in Paragraph 3. (Note: If installing Option CK19 hanger kit, suspension points change; see Figure 4B.)

WARNING: Suspend the heater only from the threaded hanger brackets. Do not suspend from the heater side panel.

When the heater is lifted for suspension, the bottom must be protected. If the wooden crate bottom has been removed, the bottom of the heater will have to be supported with plywood or other appropriately placed material. If the bottom is not supported, the bottom access panel could be damaged. Also, when lifting a blower unit, support the blower and motor to prevent the unit from tipping.

All blower models have legs that support the blower assembly during shipping. After

the unit is sus- pended, these legs should be removed.

Be sure that the threaded hanger rods are locked to the heater as

shown in FigureFigure 2 -

2.Suspension

Form 436, Page 6

Image 6
Contents Model FE and be Gas-Fired, Power-VentedTable of Contents Unit HeatersSpecial Installations Aircraft Hangars/ Garages Installation CodesWarranty Fan-type unit heater is connected to a duct systemDimensions Fan-Type, Power-Vented Unit Heater Dimensions inchesDimensions mm Dimensions contd Blower-Type, Power-Vented Unit Heater Dimensions inchesUncrating and Preparation Unit Heater LocationClearances & Combustion Air Suspension Clearances and Combustion Air contdSuspending the Heater 25-400 6152 18457 12305Venting Optional, Field-Installed Hanger KitsFour-Point Swivel Connectors Option CK10 See a Specific Venting Requirements read all beforeVenting contd Horizontal Vent Terminal Clearances StructureLocation all directions unless specified Manifold or Orifice Pressure Settings Gas Piping and PressuresSizing a Gas Supply Line Electrical Supply and Connections Thermostat and Thermostat ConnectionsInstructions to Check Manifold Pressure Typical Wiring Diagrams -- Pages 12 Field Control Wiring Length and GaugeModel Size Speed Form 436, Mfg P/N 98807 Rev 8, Fan Motor Adjusting Belt TensionThermostat Connections contd Blower MotorFan Control Blower Speed AdjustmentBlower Rotation Limit ControlGas Valve Combustion Air Proving SwitchBurner Air Adjustment Pilot and Ignition SystemCheck installation after start-up Check Installation and Start-UpCheck the installation prior to start-up Start-Up -- Typical Operating SequenceOptional Vertical Louvers Optional Vertical Louvers Option CD1Optional Duct Flange Option CD9 Blower Models only Sizes Range Air Deflection400 4935 550 Conversion Table Diameter to AreaModel Filter Replacement P/N Size Qty Optional Guards Options CD10 & CD12 Blower Models onlyOptional Multiple Heater Control Options CL31 & CL32 Pilot Flame Tubing Sensor Lead Burner Rack RemovalInstructions for Burner Rack Removal See Figures Burner Rack Hinged DownBurner Rack Removal contd Heat Exchanger Burner OrificesFlash Carryover Fan or BlowerOperating Gas Valve Fan contdVenter Motor Fan and Limit ControlsTroubleshooting TRO Uble PRO Bable C Ause RemedyFor Service or REPAIR, Follow These Steps in Order Name Address Phone

BE, FE specifications

Thomas & Betts, a subsidiary of ABB, is renowned for its innovative electrical products and solutions, particularly in the fields of connectors, terminals, and wiring devices. Among its extensive product lineup, the FE and BE series stand out for their exceptional performance and versatility in various applications.

The FE (Flat Eye) and BE (Blank Eye) connectors are designed to provide reliable electrical connections in demanding environments. These connectors are particularly well-suited for industrial, commercial, and residential applications, ensuring that they meet the rigorous standards required in these fields.

One of the key features of the FE and BE connectors is their robust construction. Made from high-quality materials, they are resistant to corrosion, moisture, and other environmental factors that could compromise the integrity of the connection. The connectors are engineered to withstand high temperatures and mechanical stress, making them ideal for use in harsh conditions where reliability is essential.

Moreover, the design of FE and BE connectors facilitates easy installation and maintenance. The connectors come with user-friendly features such as a clear labeling system and intuitive locking mechanisms, ensuring a secure fit and minimizing the risk of connection failure. Additionally, these connectors are compatible with various wire sizes, offering flexibility for different projects.

Technologically, Thomas & Betts has integrated advanced manufacturing processes to ensure precision and consistency in the production of FE and BE connectors. This attention to detail results in products that not only meet but often exceed industry standards, providing customers with peace of mind regarding their electrical systems.

In terms of performance, the FE and BE connectors deliver exceptional conductivity, which is critical for minimizing energy loss and ensuring efficient operation in electrical systems. This characteristic is especially important in applications where energy efficiency and reliability are paramount.

In summary, Thomas & Betts FE and BE connectors embody a perfect blend of durability, ease of use, and technological advancement. Their robust design, compatibility with various wire sizes, and resistance to environmental stressors make them a preferred choice for professionals in the electrical industry. With a commitment to quality and innovation, Thomas & Betts continues to set the standard in electrical connectivity solutions, ensuring that their products remain at the forefront of the industry.