WHITE-RODGERS
INDUSTRIAL
TEMPERATURE CONTROL
INSTALLATION INSTRUCTIONS
Operator: Save these instructions for future use!
FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS CAREFULLY BEFORE INSTALLING OR OPERATING THIS CONTROL COULD CAUSE PERSONAL INJURY AND/OR PROPERTY DAMAGE.
DESCRIPTION
On small electric ovens, these controls may be used to operate ovens directly. On ovens requiring a current greater than the capacity of the control, these controls may be used for controlling the pilot circuits of operating relays.
These controls may also be used for controlling electri- cally operated gas valves on gas fired equipment.
THESE CONTROLS MUST BE INSTALLED BY A QUALIFIED INSTALLER.
Do not exceed the specification ratings.
All wiring must conform to local and national electrical codes and ordinances.
This control is a precision instrument, and should be handled carefully. Rough handling or distorting compo- nents could cause the control to malfunction.
This control has been accurately calibrated at the factory. Any attempt to calibrate this control will void the White- Rodgers warranty.
PRECAUTIONS
CAUTION
To prevent electrical shock and/or equipment damage, disconnect electric power to system at main fuse or circuit breaker box until installation is complete.
WARNING
Do not use on circuits exceeding specified volt- ages. Higher voltages will damage control and could cause shock or fire hazard.
SPECIFICATIONS
ELECTRICAL DATA
Switch Action: S.P.S.T. – Open on Rise
Switch Rating:
25A. 120V.A.C., 20A. 240V.A.C.
125V, PILOT DUTY 600V.A.C.
THERMAL DATA
Range: 100° to 500°F (38° to 260°C)
Differential: 15°F (8°C) Fixed
Capillary Length: 6 Ft. (1.8 m)
Bulb Size: 3/16" x 9-7/8"
|
|
EMERSON ELECTRIC CO. |
|
9797 REAVIS RD., ST. LOUIS, MO. 63123 |
|
(314) | Printed in U.S.A. |
9999 HWY. 48, MARKHAM, ONT. L3P 3J3 |
|
(905) |
|
PART NO.
Replaces