Liebert CSU 3000 specifications Magnetom Harmony/Symphony Specifications

Page 1

Keeping Business in Business

CSU3000 Chiller Designed For Siemens Magnetom Harmony/Symphony

Dedicated, equipment-matched cooling supplies the proper temperature and water flow, year round.

Factory-tested, piped, wired, and charged for hassle-free start-up and operation.

Local service and parts for quick and knowledgeable maintenance and service

Optional switch-over to alternate water source provides redundant continuous operation.

Optional remote monitoring systems keep you informed of chiller operation.

Standard product ETL/CSA Certified.

ISO 9000 Certified Company.

Magnetom Harmony/Symphony Specifications

Fluid Specified

 

Water/Glycol

 

 

 

Max Heat Dissipation—BTUH (kW)

 

102,390

 

 

 

Fluid Temperature Range—°F (°C)

 

43-54 (6-12)

 

 

 

Fluid Flow Rate—GPM (l/m)

 

13 (50)

 

 

 

Fluid Pressure Drop—PSI (kPa)

 

21.8 (150)

 

 

 

 

 

 

Process Fluid Chiller Specifications

 

 

 

 

Model Number

 

CS135A

 

 

 

Fluid Circulated

 

Water

 

 

 

Net Cooling Capacity—BTUH (kW)

 

116,000 (34)

 

 

 

Leaving Fluid Temperature—°F (°C)

 

45 (7.2)

 

 

 

Fluid Flow Rate—GPM (l/m)

 

24 (91)

 

 

 

Harmony/ Symphony Pressure Drop—PSI (kPa)

 

21.8 (150)

 

 

 

Chiller Pressure Drop—PSI (kPa)

 

11.7 (81)

 

 

 

Pump Total Head—PSI (kPa)

 

56.3 (388)

 

 

 

Pump HP (kW)

 

3 (2.2)

 

 

 