Mitsubishi Electronics 9700 Series technical manual Send-out, Fault Code List

Page 59

 

 

MITSUBISHI

 

9700 SERIES UPS

 

 

 

 

 

Page Number:

 

 

ELECTRIC

 

OWNERS / TECHNICAL MANUAL

 

 

 

 

6-2

 

 

 

 

 

 

 

 

 

Fault Code List

￿

 

 

 

 

 

￿

￿

￿

 

￿

￿

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Note 11.

￿

 

 

￿

 

 

 

Note 1

Note 2

Note 3

 

Note 4

￿

 

 

Code

 

 

 

 

 

 

 

 

 

External

 

Failure

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Status massage

 

Contents

 

 

 

Guidance

Buzzer

send-out

Code No.

 

 

indication

 

 

 

 

lamp

 

 

 

 

 

 

 

 

 

 

 

contact

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

UF003

CONVERTER ABNORMAL

Preliminary charge impossible

 

 

1

[2]

Major

 

Lit up

64

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

UF007

SENSOR ABNORMAL

Converter

input

current

sensor

circuit

 

1

[2]

Major

 

Lit up

1

 

 

abnormality

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

UF052

CB1 TRIPPED

Input circuit breaker CB1 has tripped

 

 

1

[1]

Minor

 

Flicker

97

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

UF053

CB1 ABNORMAL

Input circuit breaker CB1 abnormal

 

 

1

[1]

Minor

 

Flicker

96

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

UF056

CONVERTER OVERLOAD

Converter input overcurrent

 

 

 

1

[1]

Minor

 

Flicker

192

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

UF057

CONVERTER

Overheating of converter circuit parts

 

 

1

[1]

Minor

 

Flicker

194

 

 

OVERTEMPERATURE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

UF058

COOLING FAN

Abnormality of cooling fan (converter circuit)

 

1

[1]

Minor

 

Flicker

193

 

 

ABNORMAL

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

UF059

CONVERTER ABNORMAL

Converter control circuit abnormality

 

 

1

[1]

Minor

 

Flicker

198

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

UF102

DC OVERVOLTAGE

Overvoltage of DC voltage

 

 

 

1

[2]

Major

 

Lit up

5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

UF103

DC UNDERVOLTAGE

Low voltage of DC voltage

 

 

 

1

[2]

Major

 

Lit up

6

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

UF105

SENSOR ABNORMAL

DC voltage sensor circuit abnormality

 

 

1

[2]

Major

 

Lit up

2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

UF106

DC CAPACITANCE

Electrolytic capacitor abnormality

 

 

1

[2]

Major

 

Lit up

77

 

 

ABNORMAL

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

UF107

CB2 ABNORMAL

Battery

disconnect

circuit breaker

CB2

 

1

[2]

Major

 

Lit up

66

 

 

abnormal

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

UF151

DC VOLTAGE ABNORMAL

Does not return to float voltage after power

 

2

[1]

Minor

 

Flicker

116

 

 

supply is resumed (24 hours)

 

 

 

 

 

UF152

DC VOLTAGE ABNORMAL

Does not return to equalizing voltage after

 

2

[1]

Minor

 

Flicker

117

 

 

power supply is resumed

 

 

 

 

 

 

UF153

CB2 TRIPPED

Battery disconnect

circuit

breaker CB2 has

 

1

[1]

Minor

 

Flicker

100

 

 

tripped.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

UF156

CB2 TRIPPED (BATTERY

Battery temperature abnormality (UF157) lasted

 

1

[1]

Minor

 

Flicker

107

 

 

OVERTEMPERATURE)

a long time (Note 6)

 

 

 

 

Note 5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

UF157

BATTERY

Battery temperature abnormality

 

 

2

[1]

Minor

 

Flicker

106

 

 

OVERTEMPERATURE

 

 

Note 5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

UF158

BATTERY LIQUID LEVEL

Battery solution level drop (Note 7)

 

 

2

[1]

Minor

 

Flicker

105

 

 

(Note10)

LOW

 

 

 

 

 

 

 

 

Note 5

 

 

 

 

 

UF159

DC GROUND FAULT

Grounding of DC circuit

 

 

 

1

[1]

Minor

 

Flicker

112

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

UF160

SENSOR ABNORMAL

Sensor abnormality of battery circuit

 

 

1

[1]

Minor

 

Flicker

114

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

UF161

CB2 TRIPPED (DC

Does not

return to

float voltage after

power

 

2

[1]

Minor

 

Flicker

196

 

 

VOLTAGE ABNORMAL)

supply is resumed (48 hours) (Note 6)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

UF162

BATTERY ABNORMAL

Battery abnormal detected by battery self test.

 

￿

￿

￿

 

￿

￿

 

 

 

 

 

 

 

 

 

 

 

 

 

 

UF201

INVERTER

Output overvoltage during inverter power supply

 

1

[2]

Major

 

Lit up

12

 

 

OVERVOLTAGE

(+ 15%)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

UF202

INVERTER

Output low voltage

during

inverter supply (-

 

1

[2]

Major

 

Lit up

13

 

 

UNDERVOLTAGE

15%)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

UF203

INVERTER

Inverter output overcurrent

 

 

 

1

[2]

Major

 

Lit up

26

 

 

OVERCURRENT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

UF209

52C ABNORMAL

52C not turned ON

 

 

 

 

1

[2]

Major

 

Lit up

75

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

UF210

52C ABNORMAL

52C not turned OFF

 

 

 

 

1

[2]

Major

 

Lit up

76

 

 

 

 

 

 

 

 

 

 

 

 

 

 

UF212

FAN ABNORMAL

Fan power source abnormality during operation

 

1

[2]

Major

 

Lit up

65

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

UF213

INVERTER OR

Overheating of main circuit parts

 

 

1

[2]

Major

 

Lit up

69

 

 

CONVERTER

 

 

 

 

 

 

OVERTEMPERATURE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

UF214

COOLING FAN

Abnormality of cooling fan inside panel

 

 

1

[2]

Major

 

Lit up

67

 

 

ABNORMAL

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

UF215

FREQUENT OVERLOAD!

Load switching was made frequently during

 

4

[2]

Major

 

Lit up

86

 

 

overload

 

 

 

 

 

Note5

 

 

 

UF216

SENSOR ABNORMAL

Inverter output current sensor abnormality

 

 

1

[2]

Major

 

Lit up

11

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MITSUBISHI ELECTRIC 9700 SERIES UPS

Image 59
Contents 100 225kVA Table of Contents Fuses List of TablesMain Screen List of FiguresIntroduction Important Safety Instructions350 278 350 100 General Mitsubishi Series UPS Through the UPS Module Figure OverviewInternal Static Bypass Line Figure Inverter supply at battery operation FigureMitsubishi Series UPS Mitsubishi Series UPS Electric Owners / Technical Manual DPAU-55 Control Power circuit breakerCB101 Specifications Environmental BatteryStatic Bypass Input Rating of Circuit Breakers Mccb and Fuses UPS status indicators Outside of door Operator Controls and IndicatorsOverloadyellow Battery operation yellowLED Display Load on inverter green Load on bypass yellowMenu’s Liquid Crystal DisplayOutput voltage screen Remote / Local selection START-UP Menu Operation Menu Figure13 Discharge Termination Screen Input Power Failure14 Failure indication screen Fault Indication Figure15 External Signal Terminal Block External Signal Terminal BlockTerminals 35 to 34 Overload contact OUT5 Output Contactsfor external alarm annunciationTerminals 11 to 12 Remote Inverter Start input terminal IN1 Input Contactsfor remote access of UPSTerminals 13 to 14 Power Demand Command contact input IN2 Terminals 9 to 10 Remote Inverter Stop input terminal IN0Terminals 19 to 20 Room TEMP. High contact input IN5 Terminals 15 to 16 Asynchronous Command contact input IN3Terminals 17 to 18 Battery TEMP. High contact input IN4 External communication connectorMitsubishi Series UPS Transportation and InstallationInstallation Procedure Space requirement for routine maintenanceElectric Owners / Technical Manual External Battery SupplyProcedure for Cable Connections Mitsubishi Series UPS Mitsubishi Series UPS Recommended cable size and torque requirements Pink Burndy 1UPS Terminal Designation 100, 150, 225kVA UPS module Location of bus bars and terminal blocks Detailed TerminalsWall mounted DC breaker Input UPS module Cabinet Input Cabinet UPS module Mitsubishi Series UPS Auxiliary Alarm Negative ⊕Positive BN, BP Mitsubishi Electric 9700 Series UPS Auxiliary Alarm Negative ⊕Positive Input transformer BN BP Auxiliary Alarm ⊕Positive Negative Mitsubishi Series UPS Auxiliary Alarm ⊕Positive Negative Input transformer Input UPS module CB1 AC Input A00,B00,C00 Output N50 A50 B50 C50 A50,B50 C50,N50 Mitsubishi Series UPS Inverter START/STOP Operating Procedures UPS Start-up ProcedureUPS Shutdown Procedure Electric Owners / Technical Manual Response to UPS Failure UPS FaultUPS Component Parts Parts ReplacementBattery Contact Mitsubishi Electric Automation, Inc. at Fault CodesSend-out Fault Code List88C Abnormal Number Mitsubishi Series UPS Failure Mitsubishi Electric Automation Inc 847

9700 Series specifications

The Mitsubishi Electronics 9700 Series represents a significant advancement in automation technology, specifically designed for industrial applications requiring precision and versatility. With a strong focus on performance and efficiency, this series brings together various innovative features and robust characteristics that cater to a diverse range of operational needs.

One of the standout features of the 9700 Series is its high-speed processing capability. Equipped with powerful processors, these controllers can execute complex algorithms swiftly, enabling real-time monitoring and control of industrial processes. This ensures that operations are seamless, with minimal delays, which is crucial in manufacturing environments where time is often of the essence.

The flexibility of the 9700 Series is further enhanced by its modular design. This allows users to configure the system to meet their specific needs, whether it's expanding I/O capabilities or integrating advanced communication options. The modularity also simplifies maintenance and upgrading processes, ensuring that businesses can adapt to new challenges without significant downtime or resource investment.

Connectivity is another significant aspect of the 9700 Series. With built-in support for various communication protocols, including Ethernet and serial communication, these systems can easily integrate with existing networks and devices. This interoperability is vital for creating smart factories where information seamlessly flows between machines, ultimately leading to enhanced productivity and operational insights.

Additionally, the 9700 Series incorporates advanced technologies such as predictive maintenance and diagnostics. These features utilize machine learning algorithms to analyze performance data, predicting potential failures before they occur. This proactive approach to maintenance helps reduce unplanned downtime and extends the lifespan of equipment, thereby improving overall operational efficiency.

Lastly, the user-friendly interface of the 9700 Series allows for easy operation and monitoring. The intuitive design of the software ensures that even operators with minimal technical expertise can manage and customize processes effectively. Combined with comprehensive support and documentation, Mitsubishi Electronics ensures that users can maximize the benefits of the 9700 Series technology.

In conclusion, the Mitsubishi Electronics 9700 Series stands out as a powerful solution for modern industrial automation, delivering high-speed processing, flexibility, connectivity, and advanced diagnostic capabilities. This makes it a valuable asset for any business looking to enhance productivity and efficiency in their operations.