Home Standby – 18kW
GENERATOR |
| Model 05418 - Aluminum |
Rated Maximum Continuous Power Capacity (LP) | 18,000 Watts* | |
Rated Maximum Continuous Power Capacity (NG) | 16,000 Watts* | |
Rated Voltage | 120/240 | |
Rated Maximum Continuous Load Current |
|
|
240 Volts | 75.0 LP/66.6 NG | |
Main Line Circuit Breaker | 80 Amp | |
Phase | 1 | |
Number of Rotor Poles | 2 | |
Rated AC Frequency | 60Hz | |
Power Factor | 1 | |
Battery Requirement (not included) | Group 26, 12 Volt Negative Ground and 525 | |
Unit Weight | 451 Pounds | |
Dimensions (L” x W” x H”) | 48 x 24 x | |
Sound output in dB(A) at 23 ft. with generator at normal operating load | 66 | |
Sound output in dB(A) at 23 ft. with generator in | .................................................. 60 |
ENGINE | Model 05418 - Aluminum |
Type of Engine | GENERAC OHVI |
Number of Cylinders | 2 |
Rated Horsepower | 31.5 @ 3,600 rpm |
Displacement | 992cc |
Cylinder Block | Aluminum w/Cast Iron Sleeve |
Valve Arrangement | Overhead Valve |
Ignition System | |
Governor System | Electronic |
Compression Ratio | 9.5:1 |
Starter | 12Vdc |
Oil Capacity Including Filter | Approx. 1.7 Qts. |
Standby Operating RPM | 3,600 |
Exercise RPM | 2,400 |
Fuel Consumption |
|
Natural Gas cu.ft./hr. |
|
1/2 Load | 181.3 |
Full Load | 262 |
Liquid Propane ft3/hr (gal/hr) |
|
1/2 Load | 71.6 (1.97) |
Full Load | 103.5 (2.85) |
Required fuel pressure to generator fuel inlet at all load ranges - 5 to 7 inches of water column for natural gas, 10 to 12 inches of water column for LP gas | |
|
|
CONTROLS |
|
Mode Switch |
|
– Automatic start and stop on utility failure and return. 7 day exerciser. | |
| Cyclic cranking 7 seconds on, 7 seconds rest for 90 seconds maximum. |
– Stops unit. Power is removed from controller. | |
| Battery charger will still operate. |
– Start with starter control, unit will stay on. If utility fails, transfer will take place. |
HOME STANDBY TRANSFER SWITCH (ORDERED SEPARATELY)
Transfer Switch Rating | ........................... | 100/200/400 Amps |
Number of Poles | 2 | |
UL Listed | Yes, UL 1008 | |
Enclosure | NEMA 1 | |
.............................................................................. | NEMA 3R | |
Interrupt Rating | 10,000 Amps | |
Maximum Switching Time | 160 Milliseconds | |
Maximum Voltage | 240 Volts | |
Exercise Time | Automatic 15 Minutes Each Week |
Rating definitions - Standby: Applicable for supplying emergency power for the duration of the utility power outage. No overload capability is available for this rating. (All ratings in accordance with BS5514,
ISO3046 and DIN6271). Prime (Unlimited Running Time): Unit not recommended for prime power applications. Applicable for supplying electric power in lieu of commercially purchased power. Prime power is the maximum power available at variable load. A 10% overload capacity is available for 1 hour in 12 hours. (All ratings in accordance with BS5514, ISO3046, ISO8528 and DIN6271).* Maximum wattage and current are subject to and limited by such factors as fuel Btu content, ambient temperature, altitude, engine power and condition, etc. Maximum power decreases about 3.5 percent for each 1,000 feet above sea level; and also will decrease about 1 percent for each 12° C (10° F) above 15.5° C (60°F).