Generac Power Systems 005262-1 Miscellaneous Maintenance, ‹ Cleaning the Generator, ‹ Battery

Page 19

Standby Generator Sets

Maintenance

MISCELLANEOUS MAINTENANCE

‹CLEANING THE GENERATOR

Keep the generator as clean and as dry as possible. Dirt and moisture that accumulates on internal gen- erator windings have an adverse effect on insulation resistance.

Periodically clean generator exterior surfaces. A soft brush may be used to loosen caked on dirt. Use a vacuum system or dry, low pressure air to remove any accumulations of dirt. The generator is housed inside an all-weather enclosure, clean the enclosure with a soft, damp cloth or sponge and water.

Once each year have the generator cleaned and inspected by an Authorized Service Dealer. That dealer will use dry, low pressure air to clean internal windings. Parts inside the control console should be cleaned and inspected at this time as well.

Finally, have the insulation resistance of stator and rotor windings checked. If insulation resistances are excessively low, the generator may require drying.

‹BATTERY

All lead-acid storage batteries discharge when not in use. Refer to specific instructions and warnings that accompany the battery. If such information is not available, observe the following precautions when handling a battery:

DO NOT use jumper cables and a booster battery to crank or start the generator engine.

DO NOT recharge a weak battery while it is installed in the generator. Remove battery from generator and recharge in a well-ventilated area, away from fuel vapors, sparks, heat or flames.

Battery electrolyte fluid is an extremely caustic sulfuric solution that can cause severe burns. DO NOT permit fluid to contact eyes, skin, clothing, painted surfaces, wiring insulation, etc. If any bat- tery fluid is spilled, flush the affected area with clear water immediately.

Always wear safety glasses, rubber apron and gloves when handling a battery.

Batteries give off explosive hydrogen gas while charging. The gas can form an explosive mixture around the battery for several hours after charging. Any spark, heat or flames can ignite the gas and cause an explosion which can shatter the battery, causing blindness or other serious injury.

‹BATTERY MAINTENANCE

The battery should be inspected per Section 4.7, Scheduled Maintenance. The following procedure should be followed for inspection:

1.Inspect the battery posts and cables for tightness and corrosion. Tighten and clean as necessary.

2.Check the battery fluid level of unsealed batteries and, if necessary, fill with DISTILLED WATER ONLY. DO NOT USE TAP WATER IN BATTERIES.

3.Have the state of charge and condition checked. This should be done with an automotive-type bat- tery hydrometer.

DANGER

Storage batteries give off explosive hydrogen gas. This gas can form an explosive mixture around the battery for several hours after charg- ing. The slightest spark can ignite the gas and cause an explosion. Such an explosion can shat- ter the battery and cause blindness or other injury. Any area that houses a storage battery must be properly ventilated. Do not allow smok- ing, open flame, sparks or any spark producing tools or equipment near the battery.

Battery electrolyte fluid is an extremely corro- sive sulfuric acid solution that can cause severe burns. Do not permit fluid to contact eyes, skin, clothing, painted surfaces, etc. Wear protective goggles, protective clothing and gloves when handling a battery. If fluid is spilled, flush the affected area immediately with clear water.

Do not use any jumper cables or booster battery to crank and start the generator engine. If the battery has completely discharged, remove it from the generator for recharging.

Be sure the AUTO/OFF/MANUAL switch is set to the OFF position, before connecting the battery cables. If the switch is set to AUTO or MANUAL, the generator can crank and start as soon as the battery cables are connected.

Be sure the 120VAC power supply to the battery is turned OFF, or sparking may occur at the bat- tery posts as the cables are attached and cause an explosion.

‹BATTERY REPLACEMENT

When replacing batteries, use the same number and the type of battery that follows:

 

BCI Group No.

CCA

 

 

26

525 @ 0 deg. F

 

 

 

 

 

NOTE:

04/06

0 .Rev Maint012

The BCI number should be located directly on the battery.

10-4

Image 19
Contents Model Standby Generator Sets Table of Contents  Warning   Electrical Hazards  Introduction ‹ Operation and Maintenance‹ HOW to Obtain Service Authorized Service Dealer Location‹ Data Label Identification RecordEngine OIL Recommendations Equipment DescriptionCoolant Recommendations Engine Protective Devices ‹ LP Fuel System Fuel System‹ Fuel Requirements ‹ Natural GAS Fuel SystemSpecifications ‹ Cold Weather KIT ‹ Reconfiguring the Fuel SystemGenerator AC Lead Connections Alternator Power Winding Connections‹ FOUR-LEAD, SINGLE-PHASE Stator ‹ 3-PHASE AlternatorsPreparation Before START-UP InstallationInitial Inspection for QT Genset Startup ‹ Preparation for START-UP START-UP Checklist‹ START-UP Inspection ‹ Retransfer and Shutdown Operating Unit with Manual Transfer SwitchGenerator Control Operation ‹ Engine START-UP and TransferChecking Fluid Levels Cooling SystemMaintenance Owner Operator can Perform ‹ Changing Engine OIL ‹ Changing the Engine AIR Cleaner ‹ Coolant Change‹ Spark Plugs ‹ Battery Maintenance Miscellaneous Maintenance‹ Cleaning the Generator ‹ BatteryKW 150 KW Standby GAS Engine Driven Generator Sets Service ScheduleMaintenance Level 11-3 11-4 Problem Cause Correction Troubleshooting GuideStandby Generator Sets Page PAN CB Conn BOX Page UL Circuit Breaker QJ-2P Page Instr Hypot Test not Shown Page Components Included in 0F9696E Page Components Included in 0G1290E Page Weldment Frame 2.4L C2 Page Battery Tray C1 CPL Page Gasket Bosch 32 Page Engine 2.4L G2 Rework Page Weldment Radiator Support 2.4L Page Flange Fuel Inlet Page Rear Wrap C2 CPL Page Bracket Muffler Page Page Page Page Page Page Page Page Page Page Page C2 Units Standby Generator Sets Warranty

005262-1 specifications

Generac Power Systems 005262-1 is a highly regarded portable generator known for its reliable performance and advanced technologies. Designed to meet a variety of power needs, this generator is ideal for both residential and commercial applications, especially during power outages or outdoor events where electricity access is limited.

One of the key features of the Generac 005262-1 is its powerful 7,500 running watts and 9,375 starting watts, making it capable of powering essential appliances, tools, and equipment during times of need. This robust wattage ensures that users can operate multiple devices simultaneously without worry.

Equipped with a Generac OHV engine, the generator boasts a durable and efficient design that enhances performance while maximizing fuel efficiency. It operates on gasoline, offering approximately 11 hours of run time at half load, which is particularly valuable for extended outages or prolonged usage scenarios. The engine is designed to shut off automatically when low oil levels are detected, protecting it from potential damage and ensuring longevity.

The 005262-1 features a steel frame with foldable handles and wheels, promoting portability and ease of transport. This thoughtful design allows users to easily move the generator to wherever it is needed, making it perfect for outdoor events, job sites, or emergency situations. The generator also comes with a 10-inch wheel kit, enhancing mobility over different terrains.

Additionally, Generac offers PowerRush technology in the 005262-1 model. This innovative feature provides users with a substantial increase in starting capacity, enabling the generator to handle heavy loads more effectively, especially when first powering up equipment.

Safety and convenience are also prioritized with various outlets, including a 120V 30A twist-lock outlet and multiple 120V 20A household outlets, allowing for diverse connectivity options tailored to specific power needs.

In summary, the Generac Power Systems 005262-1 stands out due to its powerful output, advanced engine technology, portable design, and user-friendly features. Whether needed for home backup power, recreational activities, or on-site job use, this generator remains a trusted choice for dependable electricity supply. Its combination of performance, efficiency, and safety makes it a worthy investment for anyone seeking a reliable power solution.