Samsung ماكس بلس AR18HCFNBWK Final check and trial operation, Pump down procedure (when removing the product)

AR12HCFNBWK/MG, AR12HCFNBWKNMD, AR12HCFNBWKNMG, AR12HCFNBWKXMG, AR12HPFNBWK/MG, AR12HPFNBWKNMG, AR12HPFNBWKXMG, AR18HCFNBGM/MG, AR18HCFNBGMNMD, AR18HCFNBGMNMG, AR18HCFNBGMXMG, AR18HCFNBWK/MG, AR18HCFNBWKNMD, AR18HCFNBWKNMG, AR18HCFNBWKXMG, AR18HCFSBWKNMD, AR18HCFSBWKNMG, AR18HCFSBWKXMG, AR18HPFNBGM/MG, AR18HPFNBGMNMG, AR18HPFNBGMXMG, AR18HPFNBWK/MG, AR18HPFNBWKNMG, AR18HPFNBWKXMG, AR18HPFSBWK/MG, AR18HPFSBWKNMG, AR18HPFSBWKXMG, AR24HCFNBGM/MG, AR24HCFNBGMNMG, AR24HCFNBGMXMG, AR24HCFNBWK/MG, AR24HCFNBWKNMG, AR24HCFNBWKXMG, AR24HCFSBWK/MG, AR24HCFSBWKNMG, AR24HCFSBWKXMG, AR24HPFNBGM/MG, AR24HPFNBGMNMG, AR24HPFNBGMXMG, AR24HPFNBWK/MG, AR24HPFNBWKNMG, AR24HPFNBWKXMG, AR24HPFSBWK/MG, AR24HPFSBWKNMG, AR24HPFSBWKXMG

1 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54
Download on canonical page 54 pages, 0 b

Final check and trial operation

To complete the installation, perform the following checks and tests to ensure that the air conditioner operates correctly.

Check the followings:

Strength of the installation site

Tightness of pipe connection to detect gas leak

Electric wiring connection

Heat-resistant insulation of the pipe

Drainage

Grounding conductor connection

Correct operation (follow the steps below)

1. Press the Power button and check the following:

The indicator on the indoor unit lights up.

The airflow blade opens and the fan gears up for operation.

2. Press the Mode button to select Cool or Heat mode.

In Cool mode, use Temp hr. + or button and set the temperature at 16 °C. In Heat mode, use Temp hr. + or button and set the temperature at 30 °C.

• Approximately 3~5 minutes later, outdoor unit will start to operate and the

Cool or Warm air will blow out.

• After 12 minutes of stationary condition check the indoor unit air treatment.

Cooling mode (indoor unit check) Inlet air temp. - Outlet air temp: From 10 °C to 12 °C (indicative delta T)

Heating mode (indoor unit check) Outlet air temp. - Inlet air temp: From 11 °C to 14 °C (indicative delta T)

In heating mode, the indoor fan motor can remain off to avoid cold air blown into conditioned space.

3.Press the Air swing button and check the following:

The airflow blades work properly.

4.Press the Power button to stop the operation.

• When you complete the installation successfully, hand over this manual to the user for storage in a handy and safe

place.

Pump down procedure (when removing the product)

1.Press the Power button on the indoor unit for 5 seconds. Beep will sound immediately to let you know that the product is ready for pump down procedure.

2 . Release the valve caps on High and Low pressure side.

3 . Use L wrench to close the valve on the high pressure side.

4 . After approximately 2 minutes, close the valve on the low pressure side.

5 . Stop operation of the air conditioner.

6 . Disconnect the pipes.

English-51