A.O. Smith VW-500 through VW-1000 Recovery Capacities, ACGSS02307, Other Vf Boiler Features, Flow

Models: ACGSS02307 VW-500 through VW-1000

1 4
Download 4 pages 53.04 Kb
Page 2
Image 2
OTHER VF™ BOILER FEATURES:

UP TO 88% EFFICIENT, HOT WATER SUPPLY BOILER WITH MODULATING FIRE 4:1 TURNDOWN

CATEGORY IV LISTED

Requires AL29-4C gas tight rust resistant venting material

PROFESSIONAL START-UP SERVICE FURNISHED

Assures optimum performance for each installation

MEETS ASHRAE/IESNA 90.1-1999

5 YEAR HEAT EXCHANGER WARRANTY

For complete information, consult written warranty or contact A. O. Smith

OTHER VFBOILER FEATURES:

ASME 160# W.P.

ASME PRESSURE RELIEF VALVE 125#

FACTORY MOUNTED FLOW SWITCH

MEETS CSD-1 CODE-–FACTORY STANDARD

BRASS DRAIN VALVE

LOW GAS PRESSURE SWITCH

DIGITAL INLET/OUTLET TEMPERATURE READ OUT

MANUAL RESET HI-LIMIT

ALL BRONZE FACTORY MOUNTED PUMP

VFBOILER APPROVED OPTIONS:

SEQUENCING PANEL

ALARM BELL

SIDEWALL VENT KITS

VERTICAL AND HORIZONTAL DIRECT VENT KITS

SKID-MOUNTED SYSTEMS

DRY CONTACTS FOR ANY BOILER FAILURE

LOW WATER CUTOFF

LP GAS

CUPRO-NICKEL HEAT EXCHANGER TUBES

VERSATILE MULTI-VENTING CONFIGURATIONS

DIRECT-VENTING

SIDEWALL VENTING

CONVENTIONAL

 

VENTING

Please consult latest edition of the Installation Manual for detailed venting information and maximum/minimum venting distances.

RECOVERY CAPACITIES

 

Input

 

 

Temperature Rise - °F (°C)

 

 

 

 

 

 

 

 

 

 

 

 

Model

Water

40

60

80

90

100

 

120

140

Rating

 

 

 

 

 

 

 

 

 

No.

Btu/hr

Flow

(22)

(33)

(44)

(90)

(56)

 

(67)

(78)

VW-500

500,000

GPH

1,268

845

634

563

507

 

423

362

 

 

 

 

 

 

 

 

 

LPH

4,797

3,198

2,399

2,132

1,919

 

1,599

1,371

 

 

 

 

 

 

 

 

 

 

 

 

 

 

VW-750

750,000

GPH

1,901

1,268

951

845

761

 

634

543

 

 

 

 

 

 

 

 

 

LPH

7,196

4,797

3,598

3,198

2,878

 

2,399

2,056

 

 

 

 

 

 

 

 

 

 

 

 

 

 

VW-1000

1,000,000

GPH

2,535

1,690

1,268

1,127

1,014

 

845

724

 

 

 

 

 

 

 

 

 

LPH

9,595

6,397

4,797

4,264

3,838

 

3,198

2,741

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NOTE: Maximum gas supply pressure: 11˝ W.C. natural gas, 13.8˝ propane

Minimum gas supply pressure: 4˝ W.C. natural gas, 8˝ propane

Electrical Power: 120 Volts, 60 Hertz, 30 Amps.