FIBER OPTIC CONNECTOR AND ADAPTER
CLEANING AND MATING INSTRUCTIONS
Summary: The performance of an optical fiber system is largely dependent on the fiber connector cleaning procedures performed before installation. This procedure provides instructions for cleaning and mating optical fibers.
1.Assemble the following required cleaning materials, as shown in Figure
•
•Cotton tipped swabs
•Isopropyl alcohol in a pressurized dispenser
•
•Clean, dry,
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| DR | 100 |
|
|
|
|
|
|
|
|
|
| PIPE | |||
| MAHLFLF |
|
|
| B | KU |
|
| SIX INCH |
|
|
| ISO PR O PYL |
|
| CLEANERS | |||||||||||
|
| FLF |
|
|
|
|
|
|
|
|
|
|
|
| AL CO HO L |
|
|
| SDLJF;LETHIEDF |
| |||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||||
|
|
|
| BKU | HL |
|
|
|
|
|
|
|
|
|
|
|
| PLAISOP OPYLCOL |
|
|
|
|
| ||||
|
|
|
| MA |
|
|
|
|
|
|
|
|
|
|
|
| PLAISOPROPYLCOL |
|
|
| ASKLHF; SDA |
| |||||
|
|
|
|
|
|
|
|
|
|
|
| SINGLE TIPPED |
|
|
| PRO |
|
|
| ||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| KDL | ||||||
|
|
|
|
|
|
|
|
| KUL |
|
| APPLICATIONORS |
|
|
|
|
|
|
|
|
|
|
| ||||
| MA HS |
|
|
|
|
| WLBBKUL |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
| MA H | FFAH |
|
|
|
| FBOWL |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
| SFF | OOBWBKBU H H |
| LFSL | BO |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| PIPE | |||
|
|
| MAHSSLF |
|
|
|
|
|
|
| KDLF;L |
|
|
|
|
|
|
|
| CLEANERS | |||||||
|
|
| OBWBKB UH H | MAH |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Figure
2.Clean connectors by moistening a
3.Use a
4.Blow across the end of the ferrule with clean, dry, compressed air.
5.Visually inspect the connector tip for cleanliness. If the tip does not appear to be thoroughly cleaned, repeat Steps 2, 3, and 4.
6.SC and FC adapters are cleaned by using a pipe cleaner moistened with alcohol. Insert the pipe cleaner into either end of the adapter and rotate so the inside surface of the adapter is wiped by the pipe cleaner. Repeat this procedure for the opposite end. Blow the adapter dry with clean compressed air.
7.Clean attenuators with clean, dry compressed air only. Do not use a moistened wipe or pipe cleaner.
8.Mate the SC and FC connectors by inserting the connector into the adapter and aligning the connector key with the adapter key slot.