ADCP-61-471 • Issue 4 • June 2000 • Section 2: Operation and Maintenance

DLP-512

Page 2 of 2

11.Perform the end-to-end test and verify error-free data.

Reference: DLP-510ODS2 Distribution System and QFLC/QLX Chassis End-to-End

Tests

Reference: DLP-520HLXC and HLXR End-to-End Tests

Reference: DLP-522DLX- or RLX-Equipped Circuit End-to-End Tests

12.Insert partially removed DS3 MUX back into the chassis until it is properly seated.

13.Verify that STATUS indicator on offline DS3 MUX is green and its ONLINE indicator is extinguished.

Stop! You have completed this procedure.

2-50

© 2000, ADC Telecommunications, Inc.