ADTRAN 4303 DC specifications FRONT PANEL LEDs, Functionality, Installation, Specifications, 0210

Models: 4303 DC

1 2
Download 2 pages 41.42 Kb
Page 1
Image 1
TOTAL ACCESS ® 4303 DC POWER SUPPLY

TOTAL ACCESS ® 4303 DC POWER SUPPLY

JOBAID

61200335L1-22A

 

0210

 

 

DC SUPPLY

DCLEI: SLPOCD0C_ _

SUPPLY1200335L1TEMPPOWER

#61200335L1-22A#

FRONT PANEL LEDs

POWER

Off

Both -48V fuses blown, power not supplied to the shelf, or

 

 

incorrect polarity on the voltage supplied to the shelf

 

Green

Power supplied is the correct voltage and polarity; backplane

 

 

and hot insertion voltages correct

 

Amber

-48 V input and hot insertion voltage present; no backplane

 

 

voltage

 

Red

-48 V input present; no backplane voltage and no hot

 

 

insertion voltage

TEMP

Off

Normal

 

Red

Over-temperature condition

FUNCTIONALITY

The Total Access 4303 DC Power Supply furnishes the voltages necessary for proper backplane operation. The DC Power Supply also provides the voltages that enable hot insertion of the option cards and SCUs. The DC Power Supply does not, however, provide the voltages necessary to power individual option cards or the SCUs as each card has itís own DC-DC supply.

In addition, the DC Power Supply in slot PS-Aprovides alarm relay output functionality. If only one DC Power Supply is used, place the DC Power Supply in PS-Ato provide alarm relay facilities. The DC Power Supply, as well as all Total Access 4303 option modules and SCUs, has protection against the wrong voltage polarity being applied to the shelf.

INSTALLATION

Insert the module into either the slot labeled PS-Aor PS-B.

When power is supplied to the shelf, verify that the Power LED is green.

If power is supplied to the shelf and the Power LED does not illuminate, remove power and verify polarity.

To verify one or both -48V supply voltages, use the SCU terminal menus (see SCU Job Aid, 61200334L1-22) and navigate the following path:

System Status/System Alarms/-48V Bus

SPECIFICATIONS

Specifications

Input Voltage

-42 to -54 DC

Operating temperature

0ºC to 50ºC

Storage temperature

-40ºC to 70ºC

Over-temperature Indication

90ºC ± 10ºC

-48V short circuit protection

Fused (1 amp)

Backplane voltage short circuit protection

Self-mending

Relative Humidity

To 95% noncondensing

Compliance

FCC Part 15, UL 60950, NEBS Level 3

Warranty

10 years

COMPLIANCE

The Total Access 4303 DC Power Supply is NRTL listed to the applicable UL standards. The Total Access DC Power Supply is to be installed in a restricted access location and in a Type “B” or “E” enclosure only.

Code

Input

Output

Power Code (PC)

F

C

Telecommunication Code (TC)

Installation Code (IC)

A

This device complies with Part 15 of the FCC rules. Operation is subject to the following two conditions: (1) This device may not cause harmful interference, and

(2)this device must accept any interference received, including interference that may cause undesired operation.

Changes or modifications not expressly approved by ADTRAN could void the user’s authority to operate this equipment.

WARRANTY

Warranty for Carrier Networks products manufactured by ADTRAN and supplied under Buyer’s order for use in the U.S. is ten (10) years. For a complete copy of ADTRAN’s U.S. and Canada Carrier Networks Equipment Warranty

(P/N 60000087-10): (877) 457-5007, Faxback Document 414.

C A U T I O N !

SUBJECT TO ELECTROSTATIC DAMAGE

OR DECREASE IN RELIABILITY.

HANDLING PRECAUTIONS REQUIRED.

■ For a complete Installation and Maintenance Practice (P/N 61200335L1-5): (877) 457-5007, faxback Document 862. Please have your fax number ready. ■

Page 1
Image 1
ADTRAN 4303 DC specifications FRONT PANEL LEDs, Functionality, Installation, Specifications, Compliance, Warranty, Jobaid