ATLAS 890 AC POWER SUPPLY

 

For more detailed documentation, visit us online at www.adtran.com

ATLAS 890 AC POWER SUPPLY

P/N 1200344L1

 

 

VB

LEDS

FRONT PANEL

Online LED

Description

Green

Power supplied is the correct voltage

 

and polarity; backplane and hot

 

insertion voltages correct.

Amber

A temperature or power failure

 

condition is active.

Status LED

Description

Green

Normal

Red (fast blink)

Power failure condition active. A

 

power failure condition takes

 

precedence over other failures; both a

 

power and temperature failure

 

condition results in a fast blinking

 

RED LED.

Amber (slow blink)

Over-temperature condition

Test LED

Description

Off

Not used

If power is applied to the ATLAS 890 unit and there is no active Controller, the front panel LEDs will be in an indeterminate state. The controller must complete its power up sequence before the LEDs are valid.

FUNCTIONALITY

The ATLAS 890 AC Power Supply furnishes the voltages necessary for proper backplane operation. The AC Power Supply also provides the voltages that enable hot insertion of the option cards and system controller modules.

Double pole/neutral fusing.

INSTALLATION INSTRUCTIONS

1.Remove the cover plates from option slots 16 and 17 by removing the two screws.

2.Ensure there is no power cord attached to the power supply.

3.Insert power supply into ATLAS 890 option slot 16. (Redundant AC power supply will occupy slots 14 and 15.)

4.Secure the thumbscrews at both edges of the power supply. Tighten with a screwdriver.

5.Connect the power cord to the unit.

6.Switch the power supply ON.

7.To view the status of the AC Power Supply, use the System Controller terminal menus (see ATLAS 890 System Controller Quick Start Guide, 61200322L1-13A) and navigate the following path:

System Status/System Alarms

SPECIFICATIONS

Input Voltage

47 to 63 Hz; 90 to 130 VAC

Operating Temperature

0 to 50 °C

Storage Temperature

-20 to 70 °C

Relative Humidity

0% to 95% noncondensing

Over-temperature

90 ± 5 °C

Indication

 

Backplane Voltage

self-mending

Short Circuit Protection

 

Compliance

FCC Part 15, UL 60950

Warranty

5 years

Quick Start Guide, 61200344L1-13B, October 2001

Technical Support 1-888-4ADTRAN (1-888-423-8726)

Copyright 2001 ADTRAN, All Rights Reserved