NOTE: The Gigabit Ethernet port is optical and therefore
are not classified as any type of port as defined in
Appendix B of GR-1089-CORE Issue 4.
The SFPGS is designed to meet the following environ-
mental classes:
ETSI EN 300 019-1-1 “Classification of
environmental conditions; Storage,” Class 1.2
ETSI EN 300 019-1-2 “Classification of
environmental conditions, Transportation,” Class 2.3
ETSI EN 300 019-1-3 “Classification of
environmental conditions, Stationary use at weather-
protected locations,” Class 3.3
The equipment is designed to function without degra-
dation during exposure to all test severities per Class 3.3.
The Small Form-Factor Pluggable Gigabit Ethernet
Single-Mode meets the EU’s RoHS Directive 2002/95/EC
and/or applicable exemptions. See www.adtran.com for
further information on RoHS/WEEE.

COMPLIANCE

CAUTION: Electrostatic Discharge (ESD) can damage
electronic modules. When handling modules,
wear an antistatic discharge wrist strap to
prevent damage to electronic components. Place
modules in antistatic packing material when
transporting or storing. When working on
modules, always place them on an approved
antistatic mat that is electrically grounded.
The SFPGS is NRTL Listed to the applicable UL
standards. The SFPGS meets or exceeds all the
applicable requirements of NEBS, Telcordia
GR-63-CORE, and GR-1089-CORE. The SFPGS
is intended for deployment in Central Office type
facilities, EEEs, EECs, and locations where the
NEC applies (for example, Customer Premises).
Install the SFPGS in an ADTRAN product located
in a restricted access location.
This device complies with Part 15 of the FCC rules.
Operation is subject to the following two conditions:
1. This device may not cause harmful interference
2. This device must accept any interference received,
including interference that may cause undesired
operation.
Changes or modifications not expressly approved by
ADTRAN could void the user's authority to operate this
equipment.
CAUTION: Per GR-1089-CORE the ADTRAN system that
the SFP is being deployed in is designed and
intended for installation as part of a Common
Bonding Network (CBN). The ADTRAN system
that the SFP is being deployed in is not designed
nor intended for installation as part of an
Isolated Bonding Network (IBN).
Per GR-1089-CORE Section 9, the SFPGS does
not have an internal DC connection between
battery return and frame ground. The SFPGS
can be installed in a DC-I (isolated) or DC-C
(common) installation. For installations where
other cards or the host system have internal
connections between battery return and frame
ground, the system would be intended for
deployment only in a DC-C installation.
The ADTRAN system chassis frame ground
terminal must be connected to an earth ground to
ensure that the metal enclosure of the SFPGS is
properly grounded via the backplane connector.
Warranty: ADTRAN will replace or repair this product within the warranty period if it does not meet
its published specifications or fails while in service. Warranty information can be found
online at www.adtran.com/warranty.
© 2008 ADTRAN, Inc. All Rights Reserved.
*61184561PG1-22A*
C A U T I O N !
SUBJECT TO ELECTROSTATIC DAMAGE
OR DECREASE IN RELIABILITY.
HANDLING PRECAUTIONS REQUIRED.
CLEI: SOOTAD9J_ _
Product P/N: 1184561PG1 Issue Date: 0804
Document P/N: 61184561PG1-22A
PRICING AND AVAILABILITY 800.827.0807
TECHNICAL SUPPORT 800.726.8663
RETURN FOR REPAIR 256.963.8722
Small Form-Factor PluggableGigabit Ethernet, Single-Mode