3.3.SETTING THE LIMITING VALUE FOR MONITORING

5

The load resistance also has to be connected externally to the current converters. Within standard default setting the following measurement values are read out: output 1 - measurement value 1, output 2 - measurement value 2, output 3 - measurement value 3. The following figure displays the principle structure and the connection diagram if using as additional measurement device.

Figure 5: Connection Diagram for Additional Measurement Device

3.2.SETTING THE NETWORK PEAK LOAD MONITORING / MEASUREMENTS:

No settings are necessary for the additional measurement device. Converters or load resistances have to be configured in a manner so that a 1V~ measurement voltage is generated at a nominal electrical current. Thus, a voltage of 10V- results at the respective analog output.

3.3.SETTING THE LIMITING VALUE FOR MONITORING

If the additional measurement device is also used as network peak load monitoring, limiting value could be set via the help of the potentiometer R310. Standard setting is 200%, the

6

potentiometer is set on right stop, whereby 100% meaning 1V~ at the measurement inputs / load resistances.

4. SAFETY NOTES

The commissioning of the unit is permitted only upon expert installation!

For this see the currently valid AEG Power Solutions operating manual of Thyro-Power Manager.

5. OPERATION

Mains voltage - Danger!

Activate the unit only if it is secured that all necessary measures for protection against electric shock are implemented.

5.1. REGULAR OPERATION

Enabling mains voltage during regular operation activates the unit. Subsequently, the green power LED H100 and the green ON LED H101 should burn. If network load optimization is used, the LEDs H201 - H210 turn ON one after another (contingent to the selected number). All measurements and functions are performed as selected.

For more information and integration of software for programming, measurement and indication please see our comprehensive and actual valid operations manual.