NRC50

SPECIFICATION

Input suply voltage

18 - 80Vdc

 

 

 

 

Nominal current

1.5A (48V input)

 

 

 

 

Battery Charge Modes

Float, Equalize (Charge modes have configurable Float Temperature Compensation curve

 

(FTC) and di/dt charge limiting)

 

 

 

 

 

 

 

Automatic programmable, or manually triggered battery test

 

 

(Test undertaken at constant discharge current)

 

Battery Test

Multiple branches battery connection test with configurable parameters

 

(manually & automatically triggered)

 

 

Battery symmetry test

 

 

Advanced battery life counter with ambient temperature integration

 

 

Battery history log

 

CONNECTIONS

 

 

Digital outputs

8 relay outputs: (expandable to 40) 80V/300mA

 

 

 

 

Alarm outputs

4 software configurable volt-free changeover relay contacts: 250Vac/4A

 

 

 

 

Analogue output

1 opto-isolated analogue output:

 

-15V to + 15V max. (software programmable limits)

 

 

 

 

 

 

Digital inputs

16 opto-isolated inputs: (expandable to 80) 0-5Vdc (12 V-70Vdc available via external interface board)

 

 

 

 

DC voltage measurement

2 voltage measurement inputs 0/60V or 0/5V link selectable

 

 

 

 

AC voltage measurement

3 voltage measurement inputs 0/20Vac

 

Communication ports

1 isolated RS485 or RS232C link selectable

 

DC current measurement

2 current + sign measurement inputs -50 mV/50 mV, -100 mV/100 mV

 

0/5 link selectable

 

 

2 current measurement inputs 0/50mV, 0/100mV, 0/5V link selectable

 

 

 

 

Temperature measurement

I2C port, up to 8 sensors

 

MAINS MEASUREMENT

 

 

Voltage

Single or three phase; range 20Vac

 

Frequency

0/60 Hz

 

 

 

 

Current (option)

Single or three phase

 

 

 

 

Communications

Direct through RS242/RS485, connection ports, optional modem* or Ethernet board*

 

(*Win50 Windows interface software package available)

 

 

 

MECHANICAL SPECIFICATION

 

 

Dimensions

88mm (2U) H, 445mm (19”) W, 245mm D

 

Weight

2.5kg to 3.6kg* (optional expansion boards)

 

Ingress protection

IP20

 

 

 

 

Mounting

Horizontal 2U, 19” racks

 

 

 

 

Connections

All rear connectors

 

ENVIRONMENTAL

 

 

Cooling

Natural convection cooling

 

 

 

 

Operating temperature

-10°C to +60°C

 

Storage temperature

-40°C to +70°C

 

Humidity

0% to 95% non condensing

 

Altitude

0 - 4000 m operating

 

STANDARDS

 

 

Safety

EN60950

 

 

 

 

EMC

Emission: EN61000-6.3/6.4 - Immunity: EN61000-6.1/6.2

 

 

 

 

Telecom networks

EN300386-2 - 300132-2

 

 

 

 

Environment

EN300019 (transportation storage and operation)

 

ROHS Directive on Restriction of use of certain Hazardous Substances

 

 

WEE directive on Waste Electrical and Electronic Equipment

 

Approvals

CE

 

AVAILABLE CONFIGURATIONS

 

 

Product references

NRC50 Alphanumeric display

 

 

 

 

yvydy. 09/11

policy of continuous development, data in this document is subject to change only after written confirmation.

from AB Electrolux.

to our

license

PS - PCM8001/1602 - EN - V1 - Due

is registered trademark used under

AEG AEG

For further information please refer to:

www.aegps.com

solar@aegps.com

Page 2
Image 2
AEG NRC50 Connections, Mains Measurement, Mechanical Specification, Environmental, Standards, Available Configurations