Additional Protection LD2: As LD3, but in addition
Smoke or Heat Alarms in all rooms or areas that
present a high fire risk to occupants.
Heat Alarms located in:
(Heat Alarms must be within 5.3m of potential fire
sources)
each Kitchen
Smoke or Heat Alarms located in:
each Living room (i.e. most frequently used
daytime room)
Smoke Alarms located:
on each storey
every 7.5 m of hallways and escape routes
within 3m of all bedroom doors
(apart from toilets & bathrooms )
for new or materially altered dwellings or existing dwellings
with poor structural fire precautions

ADDITIONAL PROTECTION

LD2

Multi Storey Dwelling LD2

Living
Room
Bedroom Bathroom
Kitchen
Bedroom Shower
Garage
BedroomBedroom BedroomKitchen / Dining RoomLiving RoomBathroom

Single Storey Dwelling LD2

Heat Alarm do not fit alarm
Ionisation or Optical
Smoke Alarm Optical Smoke Alarm
6
B16008-R0-160RC SERIES-U&C 17/1/07 11:13 AM Page 5