Additional Protection LD2: As LD3, but in addition
Smoke or Heat Alarms in all rooms or areas that
present a high fire risk to occupants.
Heat Alarms located in:
(Heat Alarms must be within 5.3m of potential fire
sources)
each Kitchen
Smoke or Heat Alarms located in:
each Living room (i.e. most frequently used
daytime room)
Smoke Alarms located:
on each storey
every 7.5 m of hallways and escape routes
within 3m of all bedroom doors
(apart from toilets & bathrooms )
for new or materially altered dwellings or existing dwellings
with poor structural fire precautions
ADDITIONAL PROTECTION
LD2Multi Storey Dwelling LD2
Living
Room
Bedroom Bathroom
Kitchen
Bedroom Shower
Garage
BedroomBedroom BedroomKitchen / Dining RoomLiving RoomBathroomSingle Storey Dwelling LD2
Heat Alarm do not fit alarm
Ionisation or Optical
Smoke Alarm Optical Smoke Alarm