4 WIRING DIAGRAM

Homerun wiring of NE-JA's

NOTES:

 

NEM master

 

NE-JA

 

 

 

 

1. The NE-JA can have the external closure

 

(NEM-40A/C)

 

 

 

 

 

 

 

 

 

 

 

 

 

option, the corrindor lamp, or both

 

 

 

 

 

 

NE-JA

 

 

 

 

 

 

 

 

 

 

 

 

connected.

 

 

 

 

 

(w/dry closure

 

 

2. When including a corridor lamp, cut

 

 

 

 

 

 

output)

NE-JA

 

 

GRN/BLK jumper, and connect NBY-4A to

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(w/corridor

 

terminals 2 and 3 on sub station.

 

 

1

 

1

 

 

lamp)

 

3. When using the extra contact, connect

 

 

 

 

2

 

 

 

 

 

input (coil) of relay to H of master and

 

 

2

 

 

 

1

 

 

 

terminal 4 at sub.

 

 

 

 

 

 

 

4. The dry closure will stay activated from the

 

 

 

 

 

 

2

 

 

 

 

 

 

 

 

 

 

 

time the call is placed until it is answered

 

 

 

 

 

 

 

 

 

 

 

 

40

 

 

 

 

1

 

 

at the master station. The RY-PA is a 12V

 

E

 

 

 

 

 

2

 

 

DC, "normally open" relay. If a "normally

 

 

 

 

 

 

 

3

GRN/BLK

 

closed" contact is required, the RY-PA can

 

 

 

Blk

 

Blk

3

4

 

be changed to N/C, or a standard 12V DC,

 

+

H

 

jumper

 

PS24

RY-PA

4

 

 

N/C relay can be used.

-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Yel

 

Blu

 

Cut the jumper

 

 

 

 

 

 

(2)

 

 

TERMINAL DEFINITIONS:

 

 

 

 

 

 

 

 

when corridor

 

Dry closure output

 

 

 

NBY-4A

 

lamp is installed

1, 2: Call-in and communication

 

for duration of call-in

 

 

 

at sub. Secure

3:

Corridor lamp activation

 

 

 

 

 

insulation.

 

 

 

 

 

 

 

 

4:

External relay activation

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Blu

 

7 SPECIFICATIONS

 

 

 

 

 

 

Blu

Blu

 

 

 

 

 

 

 

 

NAR-2A

PS24 : PS-24E. PS-2410A (USA. for up to 20 subs)

5 OPARATION

1.To place a call, press call button on door station once. The call-in tone and LED will be lit on the master station, remaining activated until answered. The LED on the door station will be lit to indicate a call has been placed.

2.When the master station answers, a brief pretone will be heard. Speak into the door station hands free.

3.When the call is completed, the person at the master will press OFF button, and communication will be cut off. The person at the remote station does nothing.

4.If a corridor lamp is included, the lamp will be lit from the time the call is placed until answered.

5.If a relay is included at the remote station to provide an extra dry closure, the closure will be activated from the time the call is placed until answered.

Power Source:

Supplied by master station

Speaker:

20 ohms

Call Annunciation: Pressing call button at remote latches call at NEM master until answered.

Communication: Hands free at sub. Master is push-to-talk

Mounting:

or VOX handset.

 

 

NE-JA flush mounts in 2-gang electrical

Wiring:

box with stainless steel cover over unit.

2 conductors homerun; or 1 common plus 1

 

 

individual per sub, looped through each sub.

 

 

Shielded cable is recommended.

 

 

In USA only; Use Aiphone #822202 or #821802 for

 

 

homerun wiring, #822206 for up to 5

 

 

stations on each run, or #822210 for up to

 

 

9 stations on each run.

 

 

Wiring Distance:

 

 

 

 

 

2 wires homerun

 

 

 

 

 

Diameter

0.65mmø

1.0mmø

AWG

22AWG

18AWG

 

Distance

110m

270m

Distance

360'

880'

 

1 wire common +1 per sub

 

 

 

(applicable for max. two NE-JA's)

 

 

 

Diameter

0.65mmø

1.0mmø

AWG

22AWG

18AWG

 

Distance

70m

170m

Distance

230'

560'

6 TECHNICAL PRECAUTIONS

Caulking seals: Do not apply any caulking seals around sub station. Water drainage holes on bottom will help water or moisture to dissipate.

Cleaning: Clean NE-JA with a soft cloth dampened with neutral household cleaner and cloth. Do not spray high-pressure water on sub station.

Dimensions: 115(4-1/2") x 116(4-1/2") x 10(1/2") (outer depth)

(H x W x D; mm)

 

115 (4-1/2")

116 (4-1/2")

10 (1/2")

RY-PA

Coil Rating: 12V DC, supplied by H terminal of master

Contact Rating: 110V AC, 1A, or up to 24V DC, 1A

WARRANTY

Aiphone warrants its products to be free from defects of material and workmanship under normal use and service for a period

of one year after delivery to the ultimate user and will repair free of charge or replace at no charge, should it become defective

upon which examination shall disclose to be defective and under warranty. Aiphone reserves unto itself the sole right to make the final decision whether there is a defect in materials and/or workmanship; and whether or not the product is within the warranty.

This warranty shall not apply to any Aiphone product which has been subject to misuse, neglect, accident, or to use in violation of instructions furnished, nor extended to units which have been repaired or altered outside of the factory.

This warranty does not cover batteries or damage caused by batteries used in connection with the unit.

This warranty covers bench repairs only, and any repairs must be made at the shop or place designated in writing by Aiphone. Aiphone will not be responsible for any costs incurred involving on site service calls.

AIPHONE CO., LTD., NAGOYA, JAPAN

AIPHONE CORPORATION, BELLEVUE, WA, USA

AIPHONE EUROPE N.V., ANTWERP, BELGIUM

NE-JA-I (E) 1201A

- 2 -

Printed in Japan (E)

 

Page 2
Image 2
Aiphone A83090 operation manual Wiring Diagram, Specifications, Oparation, Technical Precautions, Warranty