Allied Air Enterprises (2 Using Accessory Lift Kit, Typical Condensate Drain Connection, Screw

Models: 4)PCE(13 15) (2

1 13
Download 13 pages 53.12 Kb
Page 3
Image 3
Using Accessory Lift Kit

Using Accessory Lift Kit

Spreaders

Lifting Bracket

(Field Supplied)

Accessory

 

Sheet Metal

 

Screw

 

To avoid possible

 

damage to unit

 

panels from lifting

 

clevis, place

 

packing material

 

between clevis

 

and panels before

 

lifting unit.

Figure 1

dimension across the unit must be used across the top of the unit. Recommended spreader length: 3 ton and smaller package units – 44", 3.5 ton and larger units – 54".

Units may also be moved or lifted with a forklift while still in the factory-supplied packaging. The lengths of the forks of the forklift must be a minimum of 42".

Lifting Bracket CAUTION

Before lifting a unit, make sure that the weight is distributed equally on the cables so that it will lift evenly.

Roof Curb Installation

If a roof curb is used, follow the manufacturer’s Installation Instructions and be sure that all required clearances are observed (see following Clearances section).

Clearances

All units require certain clearances for proper operation and service. Refer to Table 1 for the minimum clearances to combustibles as well as minimum clearances necessary for servicing and proper unit operation.

In the U.S., units may be installed on combustible floors made from wood or class A, B, or C roof covering material. In Canada, units may be installed on combustible floors.

Service Access

Access to all serviceable components is provided by four removable panels: filter compartment, blower compartment, heater compartment, and top panel.

Condensate Drain

The PCE package unit is equipped with a 3/4" FPT coupling for condensate line connection. Plumbing must conform to local codes. Use a sealing compound on male pipe threads.

The condensate drain line must be properly trapped and routed to a suitable drain. See Figure 3 for proper drain arrangement. The drain line must pitch to an open drain or pump to prevent clogging of the line. Seal around the drain connection with suitable material to prevent air leakage into the return air system.

Ductwork

Ductwork should be designed and sized according to the

Typical Condensate Drain Connection

Unit

Drain Connection

1.00" Min.

12.00"

Max.

3.00" Min.

Roof Curb Assembly

Figure 2

Positive Liquid Seal Required

Figure 3

methods in Manual Q of the Air Conditioning Contractors of America (ACCA).

A closed return duct system shall be used. This shall not preclude use of economizers or outdoor fresh air intake. It is recommended that supply and return duct connections at the unit be made with flexible joints.

The supply and return air duct systems should be designed for the CFM and static requirements of the job. They should

506252-01

Issue 0902

Page 3 of 13

Page 3
Image 3
Allied Air Enterprises (2 Using Accessory Lift Kit, Typical Condensate Drain Connection, Roof Curb Assembly, Sheet Metal