American Power Conversion 10-40kW manual Press On the keyboard until

Models: 10-40kW

1 31
Download 31 pages 48.48 Kb
Page 13
Image 13

Stop/Start UPS and Operating the External Service Bypass

Action

Steps 1-4 apply to all the parallel systems. Note that this will switch all systems into bypass operation

1.

Press

on the keyboard

Display shows

 

2.

Press

or

on the keyboard until

Bypass operation

 

 

 

 

: NO

3.

Press

on the keyboard

Bypass operation

 

 

 

 

: YES

4.

Press

on the keyboard

 

All systems switch to bypass operation

Do not switch off any of the UPS systems until steps 5-8 have been completed

5.Check light indication on the bypass panel

6.Set the external bypass switch (Q003) to position 1

Bypass operation

Lamp indication on Bypass Panel

Green light (H003) above the bypass switch handle (Q003) lights up

Green light (H004) above the output switch handle (Q004) and green lights (H002) above the output switch handles (Q002) light up

7.

Set the output switch (Q004) to position 0

H003 switches off

 

 

H002 and H004 still on

8.

Set all output switches (Q002) to position 0

H002 and H004 still on

9.Open the front door of any one system and press the green ON and the red OFF button simultaneously

The acoustic alarm sounds for 30 secs* Repeat for (all) other system(s)

10.Set all input switches (Q001) to position 0

The red alarm LED below the display lights up and the acoustic alarm sounds for 30 secs*

Display shows

**System OFF**

*Reset the acoustic alarm by pressing the key.

 

990-4043

 

 

User Guide APC Silcon 10-40kW 400V UPS

13

Page 13
Image 13
American Power Conversion 10-40kW manual Press On the keyboard until