Site Preparation – Installation Space Requirements
16 AIS® 3000 10-40kVA, 400V, Site Preparation and Installation Manual – 990-2258
Clearance for stand-alone 352mm Enclosures
*) All physical installations must comply with all national standards.
Space requirements mm
Minimum clearance above UPS (A) 0
UPS depth (B) 854
UPS width 352
Minimum free rear space for ventilation* (D) 100
Minimum front clearance (E) 1000
No side clearance required (add width of Stabilizing Bracket for floor anchoring if
applicable)*
0
Stabilizing Bracket width 85
Total installation depth, inclusive of Front Panel, and minimum front and rear
clearances (F)
1954
(C)
(A)
(D)
Stabilizing Bracket,
left and right
UPS
(B)
(F)
(E)