AIS® 3000 10-40kVA, 400V, Site Preparation and Installation Manual – 990-2258 19
Operating Environment
Operating conditions
Heat dissipation
Audible noise
Install the UPS in an indoor, temperature-controlled area, free of conductive
contaminants.
Temperature
Range:
0° to 40°C
Keep Ventilated
Front-to-Rear
Airflow (see
space
considerations)
Relative
Humidity: <95%
Non-condensing
No Conductive
Dust or
Corrosive
Fumes
Altitude derating table:
1000m: 100% load
1500m: 95% load
2000m: 91% load
2500m: 86% load
3000m: 82% load
UPS size kW at fully charged batteries
10kVA 0.5
15kVA 0.75
20kVA 1.0
30kVA 1.5
40kVA 2.0
10-20kVA 30-40kVA
Audible noise at 100% load: (1m from the UPS) 64dBA 67dBA