4. Advanced Operations
Displaying SNMP configuration information
The Show SNMP command displays all SNMP configuration information.
SNMP support status
SNMP community strings
Trap timer value
Trap destinations
To display SNMP configuration information:
At the AmpMeter PDU: prompt, type show snmp and press Enter.
Example
The following command displays the SNMP configuration information:
AmpMeter PDU: show snmp<Enter>
SNMP Configuration
SNMP: Enabled
SET Community String: private
GET Community String: public
TRAP Community String: trap
Error Trap Repeat Time (seconds): 180
Trap Destination 1: 64.42.31.208
Trap Destination 2: (undefined)
SNMP Traps
The AmpMeter PDU supports three types of SNMP traps. Traps are enabled at the tower (T), infeed (I) or
outlet (O) level.
Trap Summary
Name Level(s) Description
Status T, I, O Operational status change
Change O Control status change
Load I Input load out of li mit
All traps include the Location of the AmpMeter PDU as defined with the Set Location command. See Creating a
location description on page 12 for more information.
Status trap
A Status trap is generated when an error condition occurs on a tower, infeed or outlet. Status traps include the
reported Status, the Location of the AmpMeter PDU, and identifier and name of the affected tower, infeed or
outlet.
Any Trap Status generates a Status trap and triggers the trap timer. A new trap is generated at the end of
every timer period until the Status returns to a non-error status.
Tower Status traps
Status Error Description
Normal Tower is working correctly
NoComm x Communication to the tower has been lost
Infeed Status traps
Status Error Description
On Infeed is on
OffError x Infeed should be on but no current is sensed at the infeed
NoComm x Communication to the infeed has been lost
Page 38 - 301-0399-3 Rev A.