Troubleshooting
Use the tables below to solve minor
Possible Cause | Procedure |
|
|
Back-UPS will not switch on
Back-UPS Storage
Before storing, charge the
Storage Temperature | Recharge Frequency | Charging Duration |
23 o to 86o F | Every 6 months | 8 hours |
86o to 113o F (30o to 45oC) | Every 3 months | 8 hours |
Very low or no utility voltage.
Check that the
Disconnect
Check the wall outlet that supplies power to the
Please contact APC Technical Support to troubleshoot the unit before returning it to APC.
Order Replacement Battery
The typical battery lifetime is
When ordering, please specify Battery Cartridge RBC2.
Battery Replacement
Battery replacement is a safe procedure. The
Please consult the "Connect Battery" diagrams (a through d) on the front page of this document when performing the following procedures:
Internal battery is not connected. | Check the battery connections. (See “Connect the Battery” under |
| “Installation” on the front page of this document. |
Computer, monitor or external disk/ | Move computer, monitor, or external drive power cord plug to the |
Battery Backup outlets. | |
Surge Only outlet. |
|
|
|
Back-UPS operates on battery although normal utility voltage exists
Disconnect |
| |
|
| |
| on the rear panel of the |
|
| ing the circuit breaker button fully inward |
|
| until it catches. |
|
The wall outlet that the |
|
|
Connect the | ||
connected to does not supply utility | electrician check the building wiring. | |
power to the unit. |
|
|
|
|
|
Back-UPS does not provide expected backup time
Unplug | |
| printers and plug them into Surge Only outlets. |
| Note: Devices that have motors or dimmer switches (laser printers, |
| heaters, fans, lamps, and vacuum cleaners, for example) should not be |
| connected to the Battery Backup outlets. |
Charge the battery. The battery charges whenever the | |
recent outage and has not had time | connected to a wall outlet. Typically, eight hours of charging time are |
to recharge. | needed to fully charge the battery from total discharge. |
| |
Battery requires replacement. | Replace battery (see Order Replacement Battery). Batteries typically |
| last |
| vated temperatures. |
|
|
A red indicator is lit
Battery is not connected properly. | Check the battery connections. Consult "Connect the Battery" under |
| "Installation" on the front page of this document. It shows how to |
| access the battery and connect the wires. |
The Overload indicator is lit if | Move one or more equipment power plugs to the Surge Only outlets. |
equipment connected to the Battery |
|
Backup outlets is drawing more |
|
power than the |
|
vide. |
|
Battery requires replacement. | The battery should be replaced within two weeks (see "Order |
| Replacement Battery"). Failure to replace the battery will result in |
| reduced |
|
|
Red indicators are flashing
Call APC for service. | |
|
|
Replace Battery indicator lit and an alarm sounds when the
Internal battery not connected. | Check the battery connections. Consult "Connect the Battery" under |
| "Installation" on the front page of this document. It shows how to |
| access the battery and connect the wires. |
|
|
1 . | While viewing the |
2 . | Slide the battery compartment cover off of the |
3 . | Grasp the tab attached to the battery and slide the battery partially out of the case. Grab the battery |
| firmly and pull it straight out. The battery wires will disconnect as the battery is pulled out (dia- |
| gram b). |
4 . | Carefully unpack the new battery. Retain the packing carton so that the old battery can be recycled. |
5 . | Insert the new battery halfway into the |
6 . | Connect the wires to the new battery as follows: |
7 . | Red Wire - to red (positive) terminal |
8 . | Black Wire - to black (negative) terminal |
9 . | Note: Small sparks at the battery terminals are normal during connection. |
10.Carefully insert the battery fully into the
11.Slide the battery compartment cover back into place.
12.The Replace Battery indicator will shut off within the
The old battery must be recycled. Deliver the battery to an appropriate recycling facility or return it to APC in the packing carton that came with the new battery. Additional recycling information is provided with the new battery.
Service
If the
If the
1 . Consult the Troubleshooting section to eliminate common problems.
2 . Verify that the circuit breaker is not tripped. A tripped circuit breaker is the most common Back- UPS problem.
3 . If the problem persists, consult APC
•When calling APC Technical Support, have the
•A
•Customers who must have the original unit back due to assigned asset tags and set depreciation schedules must declare such a need at first contact with an APC Technical Support representative.
•If the warranty has expired, there is a repair charge.
For return:
•Disconnect the red battery terminal wire from the
•Pack the
•Never use styrofoam beads for packaging. Damage sustained in transit is not covered under the warranty (insuring the package for full value is recommended).
•Write the RMA number on the outside of the package.
•Return the
Specifications
Warranty
Input Voltage (on line) Frequency Limits (on line) On Battery Waveshape Maximum Load
Typical Recharge Time
Operating Temperature
Storage Temperature
Operating and Storage Relative Humidity
Size (H x W x D)
Weight
Shipping Weight
EMI Classification
On Battery
98 - 132 Vac
47 - 63 Hz (autosensing)
Stepped Sine Wave
350 VA - 210 W 500 VA - 300 W
8 Hours
32o to 104o F (0o to 40 oC)
23 o to 113 oF
0 to 95%
6.5 x 3.6 x 11.2 inches | (16.5 x 9.2 x 28.5 cm) |
350 VA - 12.5 lb (5.7 kg) | 500 VA - 13.8 lb (6.3 kg) |
350 VA - 14.0 lb (6.4 kg) | 500 VA - 15.3 lb (7.0 kg) |
FCC/DOC Class B Certified
20 Minutes typical - desktop computer and 15 inch (38.1 cm) monitor.
The standard warranty is two (2) years from the date of purchase. APC’s standard procedure is to replace the original unit with a factory reconditioned unit. Customers who must have the original unit back due to assigned asset tags and set depreciation schedules must declare such a need at first contact with an APC Technical Support representative. APC will ship the replacement unit once the defective unit has been received by the repair department, or cross ship upon the receipt of a valid credit card number. The customer pays for shipping the unit to APC. APC pays ground freight transportation costs to ship the replacement to the customer.
APC Contact Information
USA/Canada | 1.800.800.4272 |
Mexico | 292.0253 / 292.0255 |
Brazil | 0800.12.72.1 |
Worldwide | 1.401.789.5735 |
Internet | http:\\www.apc.com |
Technical Support | http:\\www.apc.com/support |
|
|
Copyright © 2002 American Power Conversion. All rights reserved.