MX28B-400 +24V Product Manual 34 990-9218
(Table 6.4-1. Parameter Locations, Descriptions, and Default Values)
PARAMETER DESCRIPTION DISPLAY SCREENS /
DEFAULT SETTINGS
Output Relay Alarms
Output Relay 1 {1}
[SYSTEM/OUT-RLY/RLY-MAP] Output Relay 1 alarm can be “mapped” to activate other
output relays (“Ignore” activates no additional relays). Out-Rly 1 Alm m+
Ignore
Output Relay 6 {1}
[SYSTEM/OUT-RLY/RLY-MAP] Output Relay 6 alarm can be “mapped” to activate other
output relays (“Ignore” activates no additional relays). Out-Rly 6 Alm m+
Ignore
LVD SETUP
LVD1 Trip {1}
[MODULES/LVD/PARAM] LVD trip (disconnect) threshold voltage. LVD1 Trip m+
21.00 V
LVD1 Restore {1}
[MODULES/LVD/PARAM] LVD restore (reconnect) threshold voltage. LVD1 Reset m+
24.00 V
LVD1 Option {1}
[MODULES/LVD/SET-ALM] Set to “Enable” if the unit has an LVD. LVD1 Option m+
Enable
LVD2 Trip {1}
[MODULES/LVD/PARAM] LVD trip (disconnect) threshold voltage. LVD2 Trip m+
21.00 V
LVD2 Restore {1}
[MODULES/LVD/PARAM] LVD restore (reconnect) threshold voltage. LVD2 Reset m+
24.00 V
LVD2 Option {1}
[MODULES/LVD/SET-ALM] Set to “Enable” if the unit has an LVD. LVD2 Option m+
Enable
LVD Alarm
LVD1 Alarm {1}
[MODULES/LVD/SET-ALM] Sets the priority or “mapping” of an LVD Alarm. LVD1 Open Alm m+
Minor
LVD2 Alarm {1}
[MODULES/LVD/SET-ALM] Sets the priority or “mapping” of an LVD Alarm. LVD2 Open Alm m+
Minor